• Full compatibility with Apollo's XP95/Discovery and Hochiki's ESP protocols
• The ability to interconnect up to eight XFP main panels (any variant) onto a two wire RS485 network. Alternatively, up to eight XFP repeaters can be connected to a non-networked XFP main panel
• Two independently programmable conventional sounder circuits
• Two programmable inputs
• Fault output relay and three programmable relay outputs with voltage free changeover contacts
• Three zone dependency functions (A, B & C to EN54-2 Clause 7.12)
• Day/night (building occupied/unoccupied) function
• Investigation delay period function
• Individual sensitivity settings for each device
• Phased evacuation and delays to outputs facility (to EN54-2 Clause 7.11)
• Alarm counter that records the number of times the panel has been in an alarm state (to EN54-2 Clause 7.13)
• Powerful short circuit protected loop drivers, capable of supporting up to 40 loop powered 10mA sounders per loop
• Integral EN54 switch mode PSU rated @ 185-260V a.c.50/60Hz (1.4A on 16 zone panel, 3A on 32 zone panel)
• Earth fault monitoring
• Push button access code or keyswitch entry to Access Levels 2 and 3 (depending on model purchased)
• Easy to read, 80 character back-lit display
• 40 characters of custom text per device
• 999 event monitoring
• Comprehensive test facilities (to EN54-2 Clause 10) and a wide range of maintenance & commissioning functions including auto-learn loops, monitor a point, test outputs, one man walk test and loop continuity test
• Intuitive Windows based upload-download PC program that allows the system to be programmed quickly and easily