200kW VOLVO power generatoring set
USD $20,000 - $30,000 /Set
Min.Order:1 Set
Shandong Huali Electromechanical Co., Ltd.
200KW VOLVO power generatoring set
Specification of genset:
Genset model:HL200GF
Prime power: 200KW / 250KVA
Standby power: 220KW / 275KVA
Power factor: 0.8
Rated Voltage: 400/230V
Rated frequency (HZ): 50
Dimensions (mm) (L×W×H): 2800×1015×1780
Weight (kg): 2224
Specification of diesel engine:
Engine Model: TAD734GE
Manufacturer: VOLVO
Governor:ECM
Air intake way: turbocharger
Cylinders/Arrangement: 6/L
Bore× Stroke(MM): 108×130
Fuel Consumption Rate(L/h): 51.8
Lubricating oil capacity(L): 24
Coolant capacity (L): 32
Engine speed (rpm): 1500
Max Power (kW): 241
Starting Method: DC24V electrical starting
Specification of alternator:
Alternator model: HLF200
Connecting Type: 3 Phase and 4 Wires
Number of Bearing: 1
Protection Grade: IP21
Altitude: ≤1000m
Exciter Type: Brushless, Self-exciting, AVR automatic voltage regulating,100% Copper winding wire
Insulation Class: H
Telephone Influence Factor (TIF):≤50
Voltage Regulation, Steady State: ≤±1%
Transient State Voltage: ≤-15%~+20%
Control System:
Operating temperature: -20°C~60°C
Relative Humidity: 95%
Operating voltage: DC24V (range: 18-30V, pressure: 50V/5 mm )
Standard functions: Engine Control/Generator Monitoring/Generator Protection/
Engine Monitoring/Clear Text Display
Shutdown: Loss of Speed Signal,Alternator Under / Over Voltage,Alternator Under/ Over Frequency,
Mains Under / Over Voltage,Mains Under/ Over Frequency,Under / Over Speed,Low Oil Pressure,High Engine Temperature,Phase Sequence Electrical (Option),Earth Fault (Option)
Warning: Alternator Under / Over Voltage,Alternator Under/ Over Frequency,Mains Under / Over Voltage,Mains Under/ Over Frequency,Under / Over Speed,Low Oil Pressure Pre-Alarm,High Engine Temperature Pre-Alarm,High/Low Battery Voltage,Over-current,Periodic maintenance
Finished Products :
Certificates :
Trade Show :
Contact Us :