open frame 500kw daewoo genset
USD $48,700 - $60,000 /Set
Min.Order:1 Set
Shandong Huali Electromechanical Co., Ltd.
open frame 500kw daewoo genset
Specification of genset
Genset model:HL500GF
Prime power: 500KW / 625KVA
Standby power: 550KW / 687.5KVA
Power factor: 0.8
Rated Voltage: 400/230V
Rated frequency (HZ): 50
Dimensions (mm) (L×W×H): 3450×1390×1820
Weight (kg): 4200
Specification of diesel engine
Engine Model: P222LE-S
Manufacturer: DOOSAN
Governor: E
Air intake way: Turbo-charged
Cylinders/Arrangement: 12/V
Bore× Stroke(MM): 128×142
Fuel Consumption Rate(L/h): 134
Lubricating oil capacity(L): 40
Coolant capacity (L): 113
Compression ratio: NA
Displacement, total (L): NA
Net weight (kg): 500
Engine speed (rpm): 1500
Max Power (kW): 603
Starting Method: DC12V electrical starting
Specification of alternator
Alternator model: HLF500
Connecting Type: 3 Phase and 4 Wires
Number of Bearing: 1
Protection Grade: IP21
Altitude: ≤1000m
Exciter Type: Brushless, Self-exciting, AVR automatic voltage regulating,100% Copper winding wire
Insulation Class: H
Telephone Influence Factor (TIF):≤50
Voltage Regulation, Steady State: ≤±1%
Transient State Voltage: ≤-15%~+20%
Control System
Operating temperature: -20°C~60°C
Relative Humidity: 95%
Operating voltage: DC24V (range: 18-30V, pressure: 50V/5 mm )
Standard functions: Engine Control/Generator Monitoring/Generator Protection/
Engine Monitoring/Clear Text Display
Shutdown: Loss of Speed Signal,Alternator Under / Over Voltage,Alternator Under/ Over Frequency,
Mains Under / Over Voltage,Mains Under/ Over Frequency,Under / Over Speed,Low Oil Pressure,High Engine Temperature,Phase Sequence Electrical (Option),Earth Fault (Option)
Warning: Alternator Under / Over Voltage,Alternator Under/ Over Frequency,Mains Under / Over Voltage,Mains Under/ Over Frequency,Under / Over Speed,Low Oil Pressure Pre-Alarm,High Engine Temperature Pre-Alarm,High/Low Battery Voltage,Over-current,Periodic maintenance
Products Exhibition :
Workshop :
Office :
Contact Us :