Fireproof Paint For Steel Structural
Negotiable /Kilogram
Min.Order:250 Kilograms
Up to 1 and 2 hour fire rating.
Durable and decorative finish.
Fast drying time.
Green Label Product.
Bomba Approved.
Suitable for structural steel used as primer.[Apply directly to contour of primed I and H section columns, angles, channels and beams and hollow sections.
Various type of compatible primer.
It can be sealed and protected with a decorative water based top coat.
* Bomba Certificate [Malaysia Fire Department Approval] required to be apply by our brand specialist/applicator *
Theoritical Coverage
1mm WFT = 0.7mm DFT [Dry film Thickness] = 1 litre per SqM
1mm = 1000μm[microns]
Surface Burning
Flame spread 5, smoke development 35 when tested to ASTM E84.
Durometer Hardness
80 shore D when tested to ASTM D2240.
Initial Set
Approx 6 hours at 20'C and 50% RH for 0.4mm WFT.
Impact Resistance
18 kg/m when tested to ASTM D2794.
Fire Resistance
Structures protected with the coat have undergone fire resistance tests at approved independant laboratories to recognised standards throughout the world including:
- UK [BS476 : Part 21 : 1987]
- Canada and USA [ASTM E119 and ASTM E84]
- Australia [AS1530 : Part 4]
Assessed in accordance with ASFP "Fire protection for structural steel in buildings" procedures.
Storage
- Indoors in dry conditions between 10'C and 38'C.
- Protect from frost, excessive heat [above 45'C] and strong radiant sunlight.
Shelf Life
Maximum 10 months in original sealed containers.
Environmental
Do not discharge into drains, watercourses or soil.