Model | DSP10k | DSP20k | DSP30k | DSP40k | DSP60K | DSP80K | DSP100K | DSP150K | DSP200K | DSP300K | DSP400K |
Nominal capacity(KVA) | 10kva | 20kva | 30kva | 40kva | 60kva | 80kva | 100kva | 150kva | 200kva | 300kva | 400kva |
Work principle | Pure sine wave on line |
Control mode | DSP technique |
Parallel | Parallel directly (Max 8pcs) |
Work mode | Ups mode or ECO mode by you want to choose from front panel LCD |
Phase | 3phase+N+G |
Input power factor | >0.9 |
Nominal input voltage | 220/380VAC,230/400VAC,240/415VAC( 110vac/220vac option) |
Nominal input frequency | 50Hz±10%,60Hz±10% |
Output ripple | <2% |
Soft start | 0~100% 5sec |
Charge mode | constant current to constant voltage, with temp compensation; with Auto change |
Float Voltage | 432VDC |
Battery Type | maintenance-free lead acid battery |
Output voltage stability | ±1%( Stable load); ±3%( fluctuant load) |
Output frequency stability | 50Hz/60Hz<±0. 5% |
Crest factor | > 3:1 |
Output waveform distortion | Sine wave ,linear load<3%;non-linear load<5% |
Dynamic characteristics | Instant voltage<±5%(from 0 to100% ), Instant recover time<10mS |
Efficiency | >95%(full load) |
Overload Protection | 125%10 m;150%1S;200%200 ms |
Transfer time | <1mS( static switch with 0 transfer time ) |
Working environment | Temp: 0~40°C, relative humidity 30%~90 %;( 1% decrease against 100 meters’ rise. Altitude 4000m MAX) |
Cooling down method | COMPULSIVE VENTILATION(with temperature control) |
Communication Interface | RS232, RS485; optional SNMP card (for internet long distance monitor ) |
Redundancy function | Tandem hot backup or N+1 parallel |
Anti-surge capacity | 10/700μS,5KV ;8/20μS,20KA |
Protection level | IP21 |
Safety performance | Vin-n Vout-n 3000Vac, creepage<3.5mA , insulating resistance>2MΩ(500VDC) |
Noise dB | 48~55 | 55~60 | 60-65 | 65-70 |
Dimension(W×D×H)mm | 450×800×1050 | 600×800×1250 | 950×850×1800 | 1380×980×1800 | 1600×1200×1800 |
Weight(Kg) | 210 | 320 | 360 | 390 | 450 | 800 | 860 | 1280 | 1490 | 1800 | 2000 |