MODEL | AD-155B | ||
OUTPUT | OUTPUT NUMBER | CH1 | CH2 |
DC VOLTAGE | 27.6V | 27.1V | |
RATED CURRENT | 5A | 0.5A | |
CURRENT RANGE | 0~ 5.5A | 0~ 0.5A | |
RATED POWER | 151.55W | ||
RIPPLE & NOISE (max.) Note.1 | 150mVp-p | ----- | |
VOLTAGE ADJ. RANGE | CH1:24 ~ 29V | ||
VOLTAGE TOLERANCE | ±1.0% | ----- | |
LINE REGULATION | ±0.5% | ----- | |
LOAD REGULATION | ±0.5% | ----- | |
SETUP,RISE TIME | 1000ms,90ms/230VAC 2000ms, 90ms/115VAC at full load | ||
HOLD UP TIME | 24ms / 230VAC 20ms/115VAC at full load | ||
INPUT | VOLTAGE RANGE | 88~264VAC 124~370VDC | |
FREQUENCY RANGE | 47 ~ 63Hz | ||
EFFICIENCY (Typ.) | 84% | ||
AC CURRENT (Typ.) | 2.5A/115VAC 1.5A/230VAC | ||
INRUSH CURRENT (Typ.) | COLD START 20A/115VAC 40A/230VAC | ||
LEAKAGE CURRENT | <1mA / 240VAC | ||
PROTECTION | OVER LOAD | Protection type : AC Charging Mode : Constant current limiting recovers automatically after fault condition is removed UPS Mode : Protected by internal fuse | |
105 ~ 135% CH2:0.51 ~ 0.9A rated output power | |||
OVER VOLTAGE | CH1:31.74 ~ 37.26V | ||
Protection type : Shut down o/p voltage, re-power on to recover | |||
BATTERY LOW | 19.5V(+1.5V,-1V) | ||
ENVIRONMENT | WORKING TEMP. | -10~+60°C (Refer to derating curve) | |
WORKING HUMIDITY | 20~90% RH non-condensing | ||
STORAGE TEMP., HUMIDITY | -20~+85°C, 10~95%RH | ||
TEMP. COEFFICIENT | ±0.03%/°C (0~50°C)on CH1 output | ||
VIBRATION | 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes | ||
SAFETY & EMC (Note 4) | SAFETY STANDARDS | UL60950-1, TUV EN60950-1 approved | |
WITHSTAND VOLTAGE | I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC | ||
EMC EMISSION | Compliance to , EN55022 (CISPR22) Class B ; EN61000-3-2.3 | ||
EMC IMMUNITY | Compliance to EN61000-4-2,3,4,5,6,8,11,EN55024, light industry level, criteria A | ||
ISOLATION RESISTANCE | I/P-O/P,I/P-FG,O/P-FG:100M Ohms / 500VDC / 25°C/ 70% RH | ||
OTHERS | MTBF | 183.3Khrs min. MIL-HDBK-217F (25°C) | |
DIMENSION | 199*110*50mm (L*W*H) | ||
PACKING | 0.88Kg; 16pcs/15Kg/0.95CUFT | ||
NOTE | 1.Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 2.. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4The power supply is considered a component which will be installed into a final equipment. the final equipment must be re-confirmed that it still meets EMC directives.For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies. |