220v/230v/240v 0.9PF HT31series online UPS
Negotiable /Piece
Min.Order:1 Piece
INVT Power System (Shenzhen) Co., Ltd.
HT3110L | HT3115L | HT3120L | |
INPUT | |||
Cold Start | YES, default frequency=50Hz or settable | YES, default frequency=50Hz or settable | YES, default frequency=50Hz or settable |
Acceptable Input Voltage | 50%~125%(220VAC/230VAC/240VAC) | 50%~125%(220VAC/230VAC/240VAC) | 50%~125%(220VAC/230VAC/240VAC) |
100% load@80%~125% | 100% load@80%~125% | 100% load@80%~125% | |
90% load@70%~80% | 90% load@70%~80% | 90% load@70%~80% | |
80% load@60%~70% | 80% load@60%~70% | 80% load@60%~70% | |
65% load@50%~60% | 65% load@50%~60% | 65% load@50%~60% | |
Phase | Three phase in,single phase out | Three phase in,single phase out | Three phase in,single phase out |
Transfer Voltage Range | |||
-Line low transfer | 110VAC/115VAC/120VAC | 110VAC/115VAC/120VAC | 110VAC/115VAC/120VAC |
-Line low recovery | 116VAC/122VAC/127VAC | 116VAC/122VAC/127VAC | 116VAC/122VAC/127VAC |
-Line high transfer | 275VAC/288VAC/300VAC | 275VAC/288VAC/300VAC | 275VAC/288VAC/300VAC |
-Line high recovery | 268VAC/279VAC/291VAC | 268VAC/279VAC/291VAC | 268VAC/279VAC/291VAC |
Input Current | |||
-Rating(at nominal input voltage) | 17A | 25.5A | 34A |
Input Power Factor | ≥0.95 | ≥0.95 | ≥0.95 |
Input Frequency Range | 40Hz - 70Hz | 40Hz - 70Hz | 40Hz - 70Hz |
Generator | Support Any Generator | Support Any Generator | Support Any Generator |
OUTPUT | |||
Frequency adaptable | Settable | Settable | Settable |
Power | |||
-Power(kVA) max | 10 | 15 | 20 |
-Power(kW) max | 9 | 13.5 | 18 |
Output Voltage | |||
-Waveform | Pure sine wave | Pure sine wave | Pure sine wave |
-Nominal voltage | 220/230/240VAC | 220/230/240VAC | 220/230/240VAC |
-Voltage regulation | ± 1 % | ± 1 % | ± 1 % |
-Transient response | ≤5% (50% - 100% -50%) | ≤5% (50% - 100% -50%) | ≤5% (50% - 100% -50%) |
-Transient recovery | ≤15ms(0% - 100% -0%) | ≤15ms(0% - 100% -0%) | ≤15ms(0% - 100% -0%) |
-Voltage distortion | ≤1% THD, linear load | ≤1% THD, linear load | ≤1% THD, linear load |
≤5% THD, non-linear load | ≤5% THD, non-linear load | ≤5% THD, non-linear load | |
Output Frequency | |||
-Synchronization range | settable,±3Hz default | settable,±3Hz default | settable,±3Hz default |
-Slew rate | 0.5~5Hz/s,2Hz/s default | 0.5~5Hz/s,2Hz/s default | 0.5~5Hz/s,2Hz/s default |
-Battery mode | (50±0.05) Hz | (50±0.05) Hz | (50±0.05) Hz |
Transfer Time | |||
-Line mode to battery mode | 0 | 0 | 0 |
-Inverter to bypass | 0 | 0 | 0 |
Efficiency | |||
-Line mode with battery full charged | 93.0% | 93.0% | 93.0% |
-ECO mode | 98.0% | 98.0% | 98.0% |
-Battery mode | 92.0% | 92.0% | 92.0% |