awg building PVC Insulated Wire
USD $0.25 - $10 /Kilometer
Min.Order:1 Kilometer
Zhengzhou Hongda Cable Co., Ltd.
Our company is a professional manufacturer of awg building PVC Insulated Wire .We have the best R&D, production, sales and service team and modern enterprise management organization.
1. Standard:
BS6500, IEC277-5-1979
2. Application:
General purpose indoor and outdoor, electrical tools, washing machines, and vacuum cleaners etc.
3. Construction:
Flexible annealed copper conductor PVC insulated and PVC sheathed.
4. Voltage:
600V
5.specification
Name | Laying Site and Requirements | Long-time Permissible Working Temperature of Conductor(°C) |
Copper Conductor,PVC Insulated Wire | Fixed laid in the circumstance of indoor, conduit etc. | 70 |
Aluminium Conductor,PVC Insulated Wire | ||
Heat Resistant Copper Conductor,PVC Insulated Wire at 90
| Fixed laid in the circumstance of high temperature environment and can be laid indoor, conduit etc.
| 90 |
Copper Conductor,PVC Insulated Flexible Wire | Fixed laid where flexibility is required. | 70 |
Copper Conductor PVC Insulated and PVC Sheathed Round Wire | Fixed laid where high mechanical protection and moisture are required. They can be laid in the air or underground. | 70 |
Aluminium Conductor PVC Insulated and PVC Sheathed Round Wire | ||
Copper Conductor PVC Insulated and PVC Sheathed Flat Wire | ||
Aluminium Conductor PVC Insulated and PVC Sheathed Flat Wire | ||
Copper Conductor,PVC Insulated Flexible Connector | Mainly used at middle-light type movable euipments, instrument and meters, household appliances, power and lighting and the places where flexibility is required. | 70 |
Copper Conductor,PVC Insulated Flat Flexible Connector | ||
Copper Conductor,PVC Insulated Flexible Twisting Connector | ||
Copper Conductor PVC Insulated and PVC Sheathed Round Flexible Connector(Light and Common Type) |
Conductor |
| Insulation | Electrical characteristic | |||
AWG | Conductor construction NO.* ΦMM | Diameter mm | Insulatin thickness mm | Over diameter mm | Condutor resistance 20°Cohm/km | Permissible ampacity 20°C-AMR |
28 | 7*0.120 | 0.40 | 0.25 | 0.90 | 227.0 | 1.01 |
26 | 7*0.160 | 0.49 | 0.33 | 1.15 | 143.0 | 1.61 |
24 | 11*0.160 | 0.61 | 0.33 | 1.27 | 89.30 | 2.57 |
22 | 17*0.160 | 0.76 | 0.33 | 1.42 | 56.21 | 4.36 |
20 | 21*0.180 | 0.95 | 0.33 | 1.61 | 35.20 | 6.94 |
18 | 34*0.180 | 1.21 | 0.33 | 1.87 | 22.20 | 11.01 |
16 | 26*0.254 | 1.50 | 0.33 | 2.13 | 14.00 | 17.52 |
14 | 41*0.254 | 1.88 | 0.50 | 2.85 | 8.45 | 25.36 |
12 | 65*0.250 | 2.33 | 0.60 | 3.53 | 5.31 | 28.68 |
10 | 105*0.250 | 2.96 | 0.70 | 4.36 | 3.34 |