220V Battery string used to Power plant
Negotiable /Unit
Min.Order:1 Unit
Xi'an Foresight Electronics Technology Co., Ltd.
220V Battery Load Bank is specifically designed for the maintenance of the lead-acid battery discharge in the electricity sector. It is a new high-tech intelligent product that provides safe, reliable and convenient constant testing equipment for the DC system
HOST MACHINE:
ACCESSORIES :
A
Main Functions and Features:
1,Used to discharge to battery string removed from the system
2,Discharge to Battery string voltage as 220V, Cell voltage as 1.2V/2V/6V/12V
3,4 adjustable stop points and multiple alarm designs to control the discharge process intelligently
4,7inch LCD touch screen for easy operation and showing various parameters real time
5,Support RS232real time monitoring by PC or SD Card download data after discharge
6,PC software for capacity evaluation and report generation
7,Optional wireless modules for 1.2V/2V/6V/12V cells voltage real-time measuring
1,On-line monitoring setting:
Online monitoring for battery string: when the battery string is under the state of online discharge, uniform charge and floating charge, perform real-time online monitoring for all cells. The monitoring includes string voltage, cell voltage, discharge current, monitoring time of battery string, charge/discharge capacity of battery string and etc.
2. Discharge Setting:
Perform discharge of constant current taking advantage of intellectualized dummy load after the battery string is removed from system, set up the parameters of “discharge current”,“discharge time ”,“discharge capacity” ,“final protective voltage of whole pack” and“ final protective voltage of cell”, and the tester could carry out discharge function automatically, display discharge current,battery discharged capacity,the whole pack voltage, cell voltage,
Discharge time and etc at real time;
Product Type:
Different discharge current range
String Voltage | 220VDC |
Discharge current Range | 30A 60A 100A 150A 200A 300A |
Features | Specifications | ||||
Model | 220/30 | 220/60 | 220/100 | 220/200 | |
String Voltage measurement range | 0~285V | ||||
String Voltage Resolution | 0.01V | ||||
Voltage measurement accuracy | 0.5% | ||||
Cell Voltage Resolution | 0.01V | ||||
Discharge current Range | 2~30A | 2~60A | 2~100A | 2~200A | |
Discharge Voltage of Constance current and constant power | 180~280V | ||||
Resolutions | 0.1A | ||||
Current measurement resolutions | 1% | ||||
Power Supply | AC 100V- 220V±15% 50Hz/60Hz | ||||
Cooling mode | Air Cooling | ||||
Communication Mode | RS232 and SD Card | ||||
Display | 7inch Touch screen | ||||
High-Voltage insulation test | Input-The enclosure:2200Vdc 1min Input-Output:2200Vdc 1min Output- The enclosure:700Vdc 1min | ||||
Safety standard | EN610950 | ||||
Work Temperature | -5~50℃ | ||||
Storage Temperature | -40~70℃ | ||||
Humidity | Relative humidity 0~90%(40±2℃) | ||||
Noise | <60dB | ||||
Dimensions | 40x225x300mm | 480x225x410mm | 600x250x410mm | 600x225×x630mm | |
Weight | <10.5Kg | <13Kg | <15.5Kg | <25Kg |
WORK SHOP AND PRODUCT LINE:
LABORATORY:
PRODUCT INSPECTION:
APPLICATION CASE IN CLIENT'S END :
SHIPPING SERVICE: