FSIT-TV Cellcheck on line battery monitoring system
USD $1,000 - $5,000 /Set
Min.Order:1 Set
Xi'an Foresight Electronics Technology Co., Ltd.
CELLCHECKTM Intelligent Battery Monitor
Internal Resistance, Voltage and Temperature Measurements
Continuous 24/7 on-line monitoring
One CELLCHECK monitor one cell, including internal resistance, voltage and temperature
Software is available to collect data from CELLCHECK
Serial port with Optical isolation, meet MODBUS protocol, easy to be accessed by UPS controller
Easy to install without specialized training
Overview
CELLCHECK intelligent battery monitor is designed specifically for single cell. CELLCHECK combines the advanced technology with patented for the most thorough stationary battery health analysis in the industry.
Features
Full resistance, battery temperature and voltage monitoring for comprehensive battery state of health analysis
String current and ambient temperature monitoring(need TC module)
Automatic analysis of battery monitoring data, find the batteries that need replacement or maintenance
(need CM module)
Specifications
Environmental
Operating temperature:-5℃-50℃,5%-90%RH
Storage temperature: -10℃-70℃,5%-90%RH
Used for
2V,6V or 12V battery, capacity from 30AH to 2000AH
Power Requirements
CELLCHECK:powered from the battery,less than 60mA(2V) or 25mA(12V)
TC module:DC8-13V,2W
Convertor:DC8-13V,0.3W
CM module:85-264VAC,100V~370VDC,15W
Protection
Test load and power paths are fused
Measurement Range & Accuracy
String voltage:20-600V,±(0.5%+0.2V)
Cell voltage:1.5-2.5V,±(0.1%+1mV)
9-15V,±(0.1%+10mV)
Internal resistance:100-65535uΩ
Battery temperature:5℃-50℃, ±1.5℃
Ambient temperature: -10℃-+70℃,±0.5℃
String current:0-300A(optional),
±(2%+0.5A)
Communications Interfaces
CELLCHECK:serial port, meet MODBUS protocol, support 200 devices on each bus
TC module:serial port, meet MODBUS protocol
Convertor: serial port, meet MODBUS protocol
CM module:RS232, RS485, Ethernet 10/100 Mbps, meet MODBUS protocol
Insulation
2000VAC
Installation
Paste on battery or rail mounting
Weight
CELLCHECK: 115g TC module: 260g
Convertor: 40g CM module: 2.5Kg
With a big storage space to save history data
LED on panel flashes when alarms rise up which also can be read over through serial bus
All operating parameters can be set over through serial bus
Options
1. TC module
Measure string current and ambient temperature
2. CM module
Manage up to 4 strings and 200 cells each string
3. Current sensor
Measure string current with TC module
4. Software
It can be installed on PC and read and display data from CM module
A software base on PC is available to manage multiple strings, check real-time alarm and historical data