LED 3 Phase Voltage Meter / Ampere Meter PMAC600B
Negotiable /Piece
Min.Order:10 Pieces
Zhuhai Pilot Technology Co., Ltd.
Parameter | Index | |
Accuracy Rate | 0.5 | |
Suitable Network | PMAC600B: 3-phase 4-wire | |
Displayed Data | Current | 4 digits, display real value,Unit: Amp. |
Voltage | 4 digits, display real value, phase voltage, Unit:V | |
Active Power | 4 digits, display real value,Unit: KW | |
Reactive Power | 4 digits, display real value,Unit: KVAR
| |
Power Factor | 3 digits, display real value. | |
Frequency | 4 digits, display real value, Unit: Hz. | |
Active Energy | Maximum 9 digits, display real value in 3 lines, Unit: Kwh | |
Reactive Energy | Maximum 9 digits, display real value in 3 lines, Unit: Kvarh | |
Input | Rated Current | 1A or 5A (secondary) |
Rated Voltage | 380VAC | |
Frequency | 35Hz ~ 65Hz | |
Status Input | 220Vac±25%,220Vdc±25% | |
Relay Output | 220VAC/5A,30VDC/5A | |
Analog Output | 4~20mA,Maximum 400Ω | |
Power Supply | Wide | AC: 85V ~ 265V;DC: 80V ~ 300V |
Insulation Strength | 2KV(testing voltage is AC valid value) | |
Insulation Resistance | ≥ 50MΩ | |
MTBF | ≥ 50000h | |
Operating Environment | Operating Temperature:-20°C~+60°C Storage Temperature:-40°C~+85°C Humidity:5%~95%,non-condensing | |
Cut-out Dimension | 89.5mm x 89.5mm (+0.5mm) |