XJK-LG10D Controller for Refrigerated Compressed Air Dryer
Negotiable /Set
Min.Order:1 Set
Hangzhou Xinjian Electronic Co., Ltd.
Auto control the work of compressor, motor fan of condenser (based on pressure of condenser) and drain valve (based on preset value), detect 2 channels of alarm signal. It's stable, cheap and simple.
It's design for refrigerated air dryer, need pressure of condenser to control the work of motor fan of condenser.
Function: | |
Set | 3 buttons |
Display | 3 bit 0.56 inch LEDs and 5 pcs of LED lights to show work status and alarm information. |
Control | Control the work of compressor, detect and display temperature/pressure. Control the work of drain valve based on preset value. Control the work of motor fan condenser based on condenser pressure |
Alarm | 2 alarm signal input, contains overload and low pressure alarm. 6 alarm code can be displayed via LEDs |
Drain control | Turn on the drain valve 2 ways, manual or auto. |
Protect | Before turn on the compressor, the time of lock time is taken. Off the compressor when there has alarm (overload, high pressure, low pressure, pressure sensor has fault) |
Mounting | Panel mounting, size:3.4'' wide by 4.76'' tall |
Technical parameter: | |
Rating voltage | AC 220V |
Display | 3 bit LED display temperature |
Temperature accuracy | ±1°C |
Temperature detect range | -9 ~ 80°C |
Temperature sensor | NTC 103AT |
Pressure accuracy | ±5Psi |
Pressure detect range | 0 ~ 35 bar |
Pressure signal | 4 ~20 mA |
Output | 3 channels of relay (N.O), one for compressor, another for drain valve, the other for motor fan condenser |
Connection | Supply a removable connector to connect |
Function of button: | ||
NO. | Button | Definition |
1 | (Add) |
|
2 | (Minus) |
|
3 | ON/OFF | 1. in standby state, press to turn on compressor. 2. in running state, press and hold over 5 seconds to enter into set mode 3. in set mode, press to choose the next parameter 4. in set mode, press and hold over 5 seconds to save changed value and exit set mode 5. in running state, press to turn off compressor. |
Parameter definition: | ||||
---|---|---|---|---|
Code | Definition | Set range | Unit | Typical value |
1 | Low temperature of evaporator | -9 ~ 20 | °C | 0 |
2 | Max discharge pressure | 250 ~ 400 | Psi | 375 |
3 | Pressure to turn on the motor condenser | 250 ~ 400 | Psi | 300 |
4 | Pressure to turn off the motor condenser | 250 ~ 400 | Psi | 200 |
5 | Delay time to turn on auto drain | 1 ~ 10 | S | 1 |
6 | Compensation of temperature | -9 ~ 9 | °C | 0 |
7 | Drain valve on time | 1 ~ 10 | S | 2 |
8 | Drain valve off time | 1 ~ 10 | S | 8 |
9 | Lock time | 1 ~ 5 | min | 3 |
Alarm information: | |
Alarm code | Phenomenon |
E1 | Compressor overload signal is input, compressor stop work. |
E2 | Pressure of condenser too high ( pressure value > preset of ‘Max discharge pressure’), compressor stop work. |
E3 | Temperature of evaporator too low(temperature value < preset of ‘low temp. of evaporator), LED displays alarm code, compressor not stop work. |
E4 | Low pressure signal (pressure switch) is input, compressor stop work. |
E5 | Pressure sensor has fault ( no pressure signal input), compressor stop work. |
E6 | Temperature sensor has fault (temperature signal is disconnected or short connect with GND) , compressor not stop work. |