Model | DR-75-12 | DR-75-24 | DR-75-48 |
Specification | |||
DC output voltage | 12V | 24V | 48V |
Output voltage rang(Note:2) | ±2% | ±1% | ±1% |
Rated outpru current | 6.3A | 3.2A | 1.6A |
Output current range | 0-6.3A | 0-3.2A | 0-1.6A |
Wave and noise(Note:3) | 100mVp-p | 150mVp-p | 240mVp-p |
Inlet stability(Note:4) | ±0.5% | ±0.5% | ±0.5% |
Load stability(Note:5) | ±1% | ±1% | ±1% |
DC output power | 75.6W | 76.8W | 76.8W |
Efficiency | 76% | 80% | 81% |
Adjustable range for DC voltage | 10.8~13.2V | 21.6~26.4V | 43.2~52.8V |
AC input voltage range | 85~264VAC 47~63Hz;120~370DC | ||
Input current | 1.8A/115V 0.9A/230V | ||
AC Inrush current | Cold-start current 30A/115V 60A/230V | ||
Leakage current | <3.5mA/240VAC | ||
Overload proctection | 105%~150% Type:pulsing hiccup shutdown Reset:auto recovery | ||
Over-voltage protection | 13.8~16.2V | 27.6~32.4V | 58~62V |
High-temperature protection | ............... | ||
Temperature coefficient | ±0.03%/(0~50) | ||
Setup,rise,hold up time | 1000ms,60ms,50ms/230V | ||
Vibraton | 10~500Hz,2G 10min,/1cycle,period for 60min,Each axes | ||
Withsatnd voltage | Input and output internal:1.5KvAC,input and enclosure:1.5Kv AC,output and enclosure:0.5KvAC | ||
Isolation resistance | Input and output internal,input and enclosure,output and enclosure:500VDC/100M | ||
Working termperature and humidity | -10~+60(Refer to output derating vurve),20%~90%RH | ||
Store temperature and humidity | -20 +85,10%~95%RH | ||
Overall dimension | 78*93*56mm | ||
Weight | 0.27Kgs | ||
Safety standards | Meet UL 1012R requirement (Not apply for the mark) | ||
EMC standards | Meet FCC PART15 J Conduction class B | ||
Note:1.The testing condition for the paramenter above is:230VAC input,rated load,2570% RH,Temperature. | |||
2.Error.include the setting error,line stability and load stability.(Note:5) | |||
3.Wave test:adopting"A12"double wire for 20MHz and 0.1UF&47UF capacitor short-circuit for interrupting | |||
4.Inlet voltage stability test:when is over load,the lowest voltage of inlet is up to the highest voltage. | |||
5.Load stability test:The load is from 0% to 100%. |