13.2KV distribution transformer
Negotiable /Set
Min.Order:1 Set
13.2KV distribution transformer detailed information
Summarized:
S11 series oil-filled distribution transformer has hermetically sealed type distribution transformer and conservator type. This series are applicable to plant, mine, petrol chemical and other power distribution system of 6KV class, 10KV for series). This type transformer is a new type energy-saving product.
Technical data for 10KV class S11 series distribution transformer
No | Type | Rated (KVA) | Voltage combination | Vector group | Loss (KW) | No-load current (%) | IMP.VOL (%) | |||
HV (KV) | Tapping range (%) | LV (KV) | No-load loss | Full-load loss | ||||||
1 | S11-6.3 | 6.3 | 6 6.3 6.6 10 10.5 11 13.2 | ±2 X 2.5% or ±3 X 2.5% or ±5% | 0.4 or 0.415 or others | Y, yn0 or D, yn11 | 0.035 | 0.219 | 4.0 | 4.0 |
2 | S11-10 | 10 | 0.045 | 0.306 | 3.3 | 4.0 | ||||
3 | S11-15 | 15 | 0.058 | 0.360 | 2.2 | 4.0 | ||||
4 | S11-20 | 20 | 0.080 | 0.521 | 2.2 | 4.0 | ||||
5 | S11-25 | 25 | 0.090 | 0.577 | 2.1 | 4.0 | ||||
6 | S11-30 | 30 | 0.10 | 0.60 | 1.3 | 4.0 | ||||
7 | S11-50 | 50 | 0.31 | 0.87 | 1.1 | 4.0 | ||||
8 | S11-63 | 63 | 0.15 | 1.04 | 1.0 | 4.0 | ||||
9 | S11-80 | 80 | 0.18 | 1.25 | 0.9 | 4.0 | ||||
10 | S11-100 | 100 | 0.20 | 1.50 | 0.8 | 4.0 | ||||
11 | S11-125 | 125 | 0.24 | 1.80 | 0.8 | 4.0 | ||||
12 | S11-160 | 160 | 0.28 | 2.2 | 0.7 | 4.0 | ||||
13 | S11-200 | 200 | 0.34 | 2.6 | 0.7 | 4.0 | ||||
14 | S11-250 | 250 | 0.40 | 3.06 | 0.6 | 4.0 | ||||
15 | S11-315 | 315 | 0.48 | 3.65 | 0.6 | 4.0 | ||||
16 | S11-400 | 400 | 0.56 | 4.3 | 0.5 | 4.0 | ||||
17 | S11-500 | 500 | 0.68 | 5.1 | 0.5 | 4.0 | ||||
18 | S11-630 | 630 | 0.81 | 6.2 | 0.5 | 4.5 | ||||
19 | S11-800 | 800 | 0.98 | 7.5 | 0.4 | 4.5 | ||||
20 | S11-1000 | 1000 | 1.15 | 10.3 | 0.4 | 4.5 | ||||
21 | S11-1250 | 1250 | 1.36 | 12.0 | 0.3 | 4.5 | ||||
22 | S11-1600 | 1600 | 1.64 | 14.5 | 0.3 | 4.5 | ||||
23 | S11-2000 | 2000 | 1.96 | 17.8 | 0.3 | 4.5 | ||||
24 | S11-2500 | 2500 | 2.31 | 20.7 | 0.3 | 5.5 |
Plant