SenseH2-R Hydrogen Sensor Refrigerant Gas Tolerant Sensor

Brand Name NTM
Place of Origin United States
Model Number SenseH2-R
Usage Gas Sensor

Product Features

SenseH2-R Hydrogen Sensor (H2 Sensor) Features
• High sensitivity and selectivity to hydrogen
• Fast response and recovery times
• Immune to signal saturation
• Robust to widely varying ambient flow rates
• Compact and rugged design
• 1.0 to 4.5V output, spans 0.25 to 4.0% H2 in air (5 to 100% LFL)

SenseH2-R Hydrogen Sensor (H2 Sensor) Intended Uses:
The NTM SenseH2-R is intended for use as a hydrogen gas detector in the range of 0.25 to 4% hydrogen in air. This sensor is tolerant to halogen gasses commonly found in refrigerant gases and fire suppression systems.

SenseH2-R Hydrogen Sensor (H2 Sensor) Typical applications include:
• Uninterruptible power supply (UPS) systems monitoring,
• Telecom systems monitoring Stationary fuel cells ,
• Laboratory monitoring
• Motive power charging stations

SenseH2-R Hydrogen Sensor (H2 Sensor) Table of Typical Characteristics:

Metric
Min
Max
Units
Characteristics:


        H2 range (in air)
0.254.0%
        Voltage input
1224Vdc
        Output (sensing range)
1.04.5Vdc
        Error state (output signal)
0.00.75Vdc
        Error state (output signal)
4.755.00Vdc
        Power consumption (25°C)
0.100.15A
        Response time (T90)

5Sec.
        Recovery time (T10)

5Sec.
Environmental Conditions:



        Ambient temperature
-2080°C
        Relative humidity
595%R.H.
        Linear flow rate
0.025.00m/sA