Precise Measurement Acrel APM800/MA84 AC power analyzer three phase panel meter network multifunction ethernet energy meter Class 0.5S LCD display/with 8AI+4AO

Brand Name Acrel
Place of Origin China
Model Number APM800/MA84
Phase Three Phase
Output Voltage 10~230V phase voltage
Operating Temperature -20℃~65℃
Dimensions 96mm*96mm*88mm
Display Type Digital Only
Accuracy Class 0.5S class
Measuring Energy Range 0-9999

Product Features


General



APM series meters have full power measurement, energy statistics, analysis of power quality and network communications and other functions, are mainly used for comprehensive monitoring of the quality of power supply network.

                                                           Parameters

Technical Parameters

Index

Signal

Electrical network

Three-phase three-wire, three-phase four-wire, see the wiring diagram;

Frequency

4565Hz

Voltage

Rated valueAC 100V110V400V690V

Overload: 1.2 times rated value(continuous); 2 times rated value /1 second;

Power consumption:<0.5VA (per channel);

Current

Rated value: AC 1A, 5A, support 4 mm2 line access;

Overload: 1.2 times rated value(continuous); 10 times rated value/1 second;

Power consumption:<0.5VA (per channel);

Measurement accuracy

Voltagecurrent and power

class 0.5s/class 0.2s (APM800APM810/APM801)

Active power

class 0.5s/class 0.2s (APM800APM810/APM801)

Reactive power

class 2

Harmonic

1%2rd~42nd)、2%43rd~63rd

Switch inputs

Dry contact inputs, built-in power supply;

Relay outputs

Contact type: open contact in main part, changeover contact in module;

Contact capacityAC 250V/3A  DC 30V/3A

Pulse output of energy

Output mode: Optocoupler pulse with open collector;

Pulse constant40005A)、80001A) imp/kWh

Analog outputs

DC 0mA20mA4mA20mA0V5V1V5V output, accuracy class 0.5%, load resistance ≤ 500Ω;

Analog inputs

DC 0mA20mA4mA20mA0V5V1V5V iutput, accuracy class 0.5%

Storage card

Standard Capacity:4G,TF Card Up to 32G Capacity;

Communication

RS485 interface/Modbus-RTU protocol and DLT645 protocol

Profibus-DP interface/Profibus-DP protocol;

RJ45 interface (Ethernet) / Modbus-TCP, http, DHCP and other protocols;

Power supply

Working range: AC/DC 85V265V or AC/DC 115415V(P2);

Power consumption: Power consumption of the main part ≤ 15VA;

Safety

Power frequency withstand voltage

The power frequency withstand voltage between the shell and the auxiliary power supply, each input and output terminal group is AC 4kV/1min;

The power frequency withstand voltage between the auxiliary power supply and each input and each output terminal group is AC 2kV/1min;

The power frequency withstand voltage between the voltage input and other input/output terminal groups is AC 2kV/1min;

The power frequency withstand voltage between the current input and other input/output terminal groups is AC 2kV/1min;

The power frequency withstand voltage between the relay output and other input/output terminal groups is AC 2kV/1min;

The power frequency withstand voltage between each terminal group of switch input, communication, analog output and pulse output is AC 1kV/1min;

Insulation resistance

Inputsoutputs to the shell>100MΩ

Electromagnetic compatibility

Meet IEC 61000 standard (Level 4);

Protection level

Display panel IP52

Environment

Operating temperature: -20 °C ~ +65 °C;

Storage temperature: -20°C+70°C;

Relative humidity: ≤95% without condensation;

Altitude: ≤2500m;

Standards

IEC 60068-2-1

IEC 60068-2-2

IEC 60068-2-30

Environmental Testing-Part 2-1:Tests Test A:Cold IDA

Part 2-1:Tests Test B:Dry heat

Part 2-30:Tests Test Db:Damp heat,cyclic(12+12h)

IEC 61000-4

Electromagnetic compatibility-Testing and measurement techniques

IEC 61557-12

Electrical safety in low voltage distribution system up to 1000V a.c. and1500V d.c –Equipment for testing,measuring or monitoring of protective measures- Part12

Performances measuring and monitoring devices(PMD)

 IEC 62053-22

Electricity metering equipment (a.c.)-Particular requirements - Part22:Static meter for active energyclass 0.2s and 0.5s