Acrel AHKC-EKDA rated input AC0-(50-500)A output 4-20mA current type hall sensor
USD $11.9 - $11.9 /Piece
Min.Order:1 Piece
Hall current sensors are mainly used to isolate and convert Ac,DC,pulse and other complex signals .After signals are convertedaccording to the Hall Effect Theory,the can be directly acquired by AD,DSP,PLC, secondary instruments and other devices.Hall current sensors are widel applicable for acquisition and feedback control of current signals in the current monitoring,battery application,inverter,solar power management,direct current cabinet ,DC motor drive,electroplating,welding,frequency converter,UPS servo control systems.They feature the quick response ,wide range of measurement,high precision ,strong overload capcity,good linearity and excellent and anti-interference performace.
Parameters | Index |
Rated Input Current | AC0-(50-500)A |
Rated Output Voltage | 4-20mA |
Accuracy Class | 1.0 |
Power Voltage | DC12V/24V(allowable fluctuation±20%) |
Zero Offset Voltage | ±20mV |
Offset Voltage Drift | ≤±1.0mV/℃ |
Linearity | ≤0.2%FS |
Response Time | ≤5us |
Bandwidth | 0~20kHz |
Isolation Voltage | 3.5kV/50Hz/1min |
Operating Temperature | -40℃~85℃ |
Storage Temperature | -40℃~85℃ |
Consumption | ≤0.5W |
+15V—— power supply+15V
-15V ——power supply-15V (Note that power positive and negative poles cannot be inversely connected.)
M —— signal output end positive pole
G —— power ground and signal output end negative pole
Note: The specific wiring is subject to the terminal no. of object shell. 5. Precautions
1. When the Hall sensor is used, attention must be paid to the coupling between the primary side coil and
assistant side coil in order to get better dynamic characteristics and sensitivity, single conductor that should cram
the thread hole of Hall sensor module completely is proposed to use. 2. When the Hall sensor is used, the best measuring accuracy can be got under rated input current value. When
the measured current is much less than the rated value, the primary side can use multi-turns if want to obtain the
best accuracy, that is IpNp=rated ampere-turns. In addition, the temperature of the primary side feeder line cannot
be more than 80℃. 3. When the Hall current sensor is working normally, the auxiliary power supply cannot be more than ±20% of
calibration value. 4. The Hall Current sensor is strictly prohibited to be fallen from high place (≥1m) during installation and use. 5. Zero and full scale regulator potentiometer can not be adjusted. 6. Auxiliary power supply is required to be deployed voluntarily. 7. Power positive and negative poles cannot be inversely connected. 6. Order Sample
Sample 1 AHKC-EKC Hall current sensor
Auxiliary power supply:DC±15V
Input:1000A
Output:5V
Accuracy:Grade 1