Acrel AMC72L-AI/C single phase energy meter AC LCD display with RS485 communication panel mounted cut out 67*67mm

Product Features

AMC Series programmable intelligent single phase meters, adopting AC sampling technology, can measure current of single-phase grid indirectly. It can be used for local display, and connecting industrial control device to form measurement and control system. 

Using AC sampling technology, it can directly or indirectly measure the power, power, voltage, current and frequency of a single-phase or three-phase power grid. It can be used for local display, and can be connected with industrial control equipment to form a measurement and control system.

The instrument can have RS-485 communication interface and adopt Modbus-RTU protocol, with analog output, relay alarm output and switch input/output.

Technical Datasheet
Technical Parameter
Value


Input
Rated Value
AC voltage:Single phaseAC 100V,400V
Three phaseAC 100V,400V,660V(UL-L,Only 72/ 96)
AC current:AC1A,5A;
DC voltage:1000V,300V,75mV,10V;
DC current: 0-20mA,4-20mA,5A;
Overload
Voltage: 1.2 times rated value(continuous); 2 times rated value /1 second
Current:1.2 times rated value(continuous); 10 times rated value /1 second
Frequency
45Hz~65Hz
Power Consumption
Power consumption of each voltage,current input circuit is less than 0.5VA
Accuracy
Class 0.5


Function
Display
LED or LCD
Communication
RS485,Modbus-RTU protocol;(1 start bit,8 data bit,1 stop bit,no parity)
Baud Rate 2400/4800/9600/19200 bps etc.
Alarm
1 channel passive relay,contact capacity 3A/30VDC,3A/250VAC, Used for high,low,unbalance alarm etc.
Analog
DC4~20mA,( load<500Ω)
(note:Shielded wire is specially selected for the above signal input and output)
Switching
Input:4 channel or 2 channel dry contact Input,built in power supply
Output:2 channel switching output,NO relay contact,capacity:3A/30VDC,3A/250VAC
Auxiliary Supply
AC/DC 85-265V
Power Consumption
<5VA
Insulation resistance
≥ 100MΩ
Power frequency withstand voltage
Between power supply set of terminals and signal input,output set of terminals 2kV/1min (RMS)
Between the shell and all set of terminals(except the set of terminals reference voltage less than 40V) AC 4kV


Environment
Temperature
Operation: -10℃~+55℃Storage: -25°C ~+70°C
Humidity
≤95%RH,no condensation,without corrosive gas
Altitude
≤ 2500m