PXIe-1085 SAMPLER
Negotiable /Bag
Min.Order:1 Bag
PXIe-1085 SAMPLER
Product model: IOM0080T
processor
32-bit
clock frequency
72MHZ
Memory
64KB flash memory, 20KB random access memory
source
AC/DC 24V
communication
Modbus RTU (115200)
Thermal resistance RTD type
Pt1000, Ni1000, NTC, Pt100, Cu100, Cu50
Temperature resolution
0.1 ℃ (AD 16bit)
Sampling rate
Default 0.15s per channel, 8-channel cycle, filter length can be set
model
BI/DI
BO/DO
AI
AO
IOM0080T
0
0
eight
0
RTD temperature
Register Address
RTD model
Register Address
AI port
explain
forty thousand and twenty-two
forty thousand one hundred and twenty-two
one
Thermal resistor input port
forty thousand and twenty-three
forty thousand one hundred and twenty-three
two
Thermal resistor input port
forty thousand and twenty-four
forty thousand one hundred and twenty-four
three
Thermal resistor input port
forty thousand and twenty-five
forty thousand one hundred and twenty-five
four
Thermal resistor input port
forty thousand and twenty-six
forty thousand one hundred and twenty-six
five
Thermal resistor input port
forty thousand and twenty-seven
forty thousand one hundred and twenty-seven
six
Thermal resistor input port
forty thousand and twenty-eight
forty thousand one hundred and twenty-eight
seven
Thermal resistor input port
forty thousand and twenty-nine
forty thousand one hundred and twenty-nine
eight
Thermal resistor input port
Contact information: 15359293870
WhatsApp:+86 15359293870
Contact person: KELLY
Email: geabbdcs@gmail.com 386353502@qq.com
Official website:
Register Description:
1、 RTD temperature register:
Address: 4x22~4x29, signed word type data, temperature value calculated by connecting thermal resistance of channels 1-8, unit: 0.1 ℃, that is, the reading value is the temperature value amplified by 10 times. For example, reading a value of 253=25.3 ℃; Read the value -128=-12.8 ℃.
2、 RTD Model Register
1. Address: 4x122~4x129, signed word type data, access thermal resistor types for channels 1-8, each input channel can be set with its own input type. The corresponding relationship between the set values and RTD types is as follows:
Setting values
RTD model
Measuring range
0 (default)
Pt1000 (default)
Min=-50.0 ℃
Max=300.0 ℃
one
Ni1000
Min=-50.0 ℃
Max=250.0 ℃
two
NTC (Note1)
Min=-55.0 ℃
Max=125.0 ℃
three
Pt100
Min=-200.0 ℃
Max=660.0 ℃
four
Cu100
Min=-50.0 ℃
Max=150.0 ℃
five
Cu50
Min=-50.0 ℃
Max=150.0 ℃
2. Address: 4x130, signed word type data, only valid for NTC type input, shared by 1-8 channels.
NTC R value(