Products Description
AMC100-ZA
Acrel AMC100 series AC precision power distribution monitoring device is a measuring device designed specifically for power management of data center servers. The device is compact in design and can monitor the full electrical parameters, input and output switches and the status of the lightning arrester of A+B two incoming lines and 192 outgoing lines in real time. The alarm thresholds of all measurement channels can be set individually, and the outgoing line The limited event immediately triggers the system's sound and light alarms, and the high integration of the monitoring loop is realized in the volume of the traditional instrument.
Function & Parameter
Function
Instrument model | AMC100-ZA |
Bus voltage Rated | 220VAC |
Current incoming circuit Rated | Secondary 5A |
Current incoming circuit Range | 0 ~ 6 A |
Input frequency | AC4 5~65 Hz |
Measurement accuracy Incoming line | Voltage/ current level 0.2, active power/energy level 0.5, reactive power/energy level 1 |
Auxiliary power | AMC100-ZA: signal to take power (≤15W) AMC100-ZA-P220: 220V independent power supply AMC100-ZA-P24: DC 12-24V independent power supply |
Environment Temperature | Work: -20℃~150℃ Storage: -25℃~70℃ |
Switch output | 4 channels 3A 250VAC/3A 30VDC |
Switch input | 8 dry nodes |
Communication | 1 isolated RS485/Modbus-RTU to the background system 1 RS485/Modbus-RTU to touch screen 1 RS485/Modbus-RTU connection downstream module Optional 1-channel Ethernet communication function |
humidity | 20%~90% |
Temperature | -40℃~+99℃ |
Product Model
Model | Function Description |
AMC100-ZA | Measurement of A+B independent 2 channels AC three-phase inlet all electricalparameters, 8DI4DO,2 channels leakage current monitoring, 1 channel Temperatureand humidity monitoring, 2-63rd harmonic, 3 channels RS485 Modbus-RTU(1 forbranch module, 1 for HMI, 1 for Supervision System) |
AMC100-FA30 | Measurement of A+B independent 30 channels AC outlet all electrical parameters,1channel RS485 Modbus-RTU |
AMC100-FA48 | Measurement of A+B independent 48 channels AC outlet all electrical parameters, 1channel RS485 Modbus-RTU |
AMC100-ZD | Measurement of A+B independent 2 channels DC inlet,U,I,P,Q, 8DI/4DO, 1 channelTemperature and humidity monitoring,3 channels RS485 Modbus-RTU((1 for branchmodule, 1 for HMI, 1 for Supervision System) |
AMC100-FD30 | Measurement of A+B independent 30 channels DC outlet all electrical parameters, 1channel RS485 Modbus-RTU |
AMC100-FD48 | Measurement of A+B independent 48 channels DC outiet all electrical parameters, 1channel RS485 Modbus-RTU |
AMC100-FAK30 | Measurement of A+B independent 30 channels AC outlet all electrical parameters andswitch value status, 1 channel RS485 Modbus-RTU |
AMC100-FAK48 | Measurement of A+B independent 48 channels AC outlet all electrical parameters andswitch value status, 1 channel RS485 Modbus-RTU |
AMC100-FDK30 | Measurement of A+B independent 30 channels DC outlet all electrical parameters andswitch value status, 1 channel RS485 Modbus-RTU |
AMC100-FDK48 | Measurement of A+B independent 48 channels DC outlet all electrical parameters andswitch value status, 1 channel RS485 Modbus-RTU |
Parameter
Instrument model | AMC100-ZA |
Measurement parameters | Voltage, current, frequency, active power, reactive power, power factor, active energy, reactive energy, Zero-to-ground voltage, leakage current and zero sequence current, total harmonic content (THD), 2-63 harmonics, current and voltage unbalance, ambient temperature and humidity |
Bus voltage | Rated | 220VAC |
Measuring range | ±20% |
Overload | Instantaneous voltage 2 times/sec |
Current incoming circuit | Rated | Secondary 5A |
Range | 0~6A |
Overload | Continuous 1.2 times, instantaneous 10 times/sec |
Temperature and humidity | Temperature Range | -40℃~+99℃ |
Humidity Range | 20%~90% |
Input frequency | AC45~65Hz |
Measurement accuracy | Incoming line | Voltage/current level 0.2, active power/energy level 0.5, reactive power/energy level 1 |
Temperature | ±1℃ |
Humidity | ±5% |
Auxiliary power | AMC100-ZA: signal to take power (≤15W) AMC100-ZA-P220: 220V independent power supply AMC100-ZA-P24: DC 12-24V independent power supply |
Environment | Temperature | Work: -20℃~150℃ Storage: -25℃~70℃ |
Humidity | Relative humidity≤93% |
elevation | ≤2500m |
Switch output | 4 channels 3A 250VAC/3A 30VDC |
Switch input | 8 dry nodes |
Communication | 1 isolated RS485/Modbus-RTU to the background system 1 RS485/Modbus-RTU to touch screen 1 RS485/Modbus-RTU connection downstream module Optional 1-channel Ethernet communication function |
Installation Method | DIN35mm rail or bottom plate installation |
Protection level | IP20 |
Pollution level | 2 |
Security | Insulation | The insulation resistance between all terminals and the conductive parts of the shell is not less than 100MΩ |
Withstand voltage | A voltage and current signal//B voltage and current signal//switch output//isolated communication port//between other ports meet AC2kV 1min, switch input and other ports should meet AC0.5kV 1min, leakage current Should be less than 2mA, no breakdown or flashover phenomenon. |
Electromagnetic compatibility | Anti-static interference | Level 4 |
Anti-electric fast transient burst | Level 3 |
Anti-surge interference | Level 4 |
Resistance to radio frequency electromagnetic field radiation | Level 3 |
Wiring&Installation
Wiring
Installation
Dimension and Packaging
Company Profile
Acrel Co., Ltd. [Stock Code : 300286. SZ] is a high-tech enterprise concentrating on research, production, sales and services. It mainly provides systemic solutions of energy efficiency management and electrical safety for users. ‘Acrel’ is equipped with the complete production lines from cloud platform software to sensors. Until now, it has more than 8000 sets systemic solutions used in China to help users to realize energy visual management ,supply energy data services and improve electrical efficiency and safety. ‘Acrel’ has maintained steady growth since its listing in 2012. The company will adhere to the concept of ‘innovation,high-efficiency,unity and honesty’ and it provides more high-quality solutions,products and service for power system users and micro-grid.
Payment & Delivery
1.Payment: T/T 100% in advance, credit card, western union, in cash and etc. T/T 30% as deposit and the balance before shipment or against copy of B/L is acceptable with enough MOQ.
2.Delivery Arriving Time: in 3-7 working days after payment received.
3.Ways of Delivery: By sea, air, train or international courier like Fedex, TNT, DHL and UPS.
Contact