Lightning Protection-Surge protective Device-18/20 μ S Power supply surge protector

Lightning Protection-Surge protective Device-18/20 μ S Power supply surge protector

3.5 - 10 /Piece

Min.Order:50 Pieces

Supply Ability:
2000000 Piece / Pieces per Month
Port:
Shanghai
Payment Terms:
T/T L/C D/P D/A

Quick Details View All >

Brand Name:
WEIJU
Place of Origin:
China
Model Number:
WD1-60 4P

Zhejiang Weiju Electrical Technology Co., Ltd

Business license
Business Type: Manufacturer
Main Products: Surge protective Device ,Lightning protection ,Transformer ,Surge Arrester ,Prepaid Meter ,Prepaid Water Meter ,Fuse ,Electronic Engergy Meter

Product Details

Introduce

WD1 series surge protector (hereinafter referred to as SPD) is applicable to T, T, TN-C, TN-S, TN-C-S and other power supply systems with AC 50/60Hz and rated voltage of 380V to protect indirect lightning, direct lightning or other transient over-voltage surges. Class III surge protector according to EC61643-1:1998-02 standard. Type D surge protector.
SPD has common mode (MC) and differential mode (MD) protection modes.
SPD conforms to GB18802.1/1EC61643-1

Install

Installed at the junction of LPZ0A or LPZ0B area and LPZI area, 35mm standard guide rail is used for installation, and the connecting copper multi strand flexible wire is 16~35mm2.
It is usually installed at the incoming low-voltage main distribution cabinet.
The grounding wire shall be a two-color conductor of more than 10mm2, and the length shall not exceed 500mm.
In order to prevent the failure of surge protective device from affecting the normal operation of the power grid, a fuse or circuit breaker shall be connected in series to the L line protector (Note: it shall be selected according to the nominal current)

Working Principle

SPD is one port, electric shock protection, indoor fixed installation, voltage limiting type.
SPD built-in separator. When SPD fails due to overheating and breakdown, the disconnector can automatically disconnect it from the power grid and give an indication signal. The visual window displays green when the SD is working normally, and red when the SD fails to disengage.
The maximum discharge current Imax of each line can reach 60kA/80kA.

Technical Parameter


Model

WD1-60

WD1-80

WD1-60

WD1-80

Maximum Continuous Working Voltage Uc(V~)

420V

385V

275V

420V

385V

275V

420V

385V

275V

420V

385V

275V

Voltage Protection level Up(KV)

≤2.2

≤2.0

≤1.8

≤2.4

≤2.2

≤2.0

≤2.2

≤2.0

≤1.8

≤2.4

≤2.2

≤2.0

Maximum discharge current(8/20us)kA

60

80

60

80

Nominal discharge current In(8/20μs)kA

30

40

30

40

Response Time ns

<25

Protection class

IP20

The Cross Section of L/N Line mm2

10-25

16-35

10-25

16-35

The Cross Section Of PE Line mm2

16-25

25-50

16-25

25-50

Selection of fuse or circuit breaker(A)

50A、63A

50A、63A

50A、63A

50A、63A

Operating Environment℃

-40℃~+85℃

Failure Indication

Aging failure: green normal, red failure

Purpose

Primary protection of incoming line

Remarks

Other maximum continuous working voltage Uc can be customized

Overall Dimensions


Contact Supplier

Ms. Chat Now

You May Like

New Products

Recommended Products

View More View Less

Find Similar Products By Category

Electronic Components & Supplies > Other Electronic Components
Categories
Hi~