Acrel ADW310 one phase wireless 4G WIFI optional single phase smart IOT energy monitoring meter with RS485 Modbus
Negotiable
Min.Order:1
Function | Description |
Measurement (Standard) | Single-phase AC Active&Reactive Energy (both forward and backward), Active Power, Reactive Power, Current, Voltage, Frequency, Power Factor, Apparant Power, Frequency |
Measurement (Optional) | Temperature Measurement:2-channel (Live line,Neutral line) Cable Temperature Monitoring; Thermistor:NTC; Range: -40~+99℃; Accuracy:±2℃ |
Communication (Standard) | RS485 Port with Modbus-RTU protocol - 1 start bit,8 data bit,1 stop bit,no parity; Baud Rate 1200~38400 bps etc. Infrared Communication - Constant Baud Rate 1200 bps |
Communication (Optional) | 4G LTE - Normal Communicaiton Module Support: LTE-FDD: B1/B3/B5/B8; LTE-TDD:B34/B38/B39/B40/B41 4G LTE - Global Communication Module Support: LTE-FDD:B1/B3/B5/B7/B8/B20/B28; LTE-TDD:B38/B40/B41 |
WiFi - Support 2.4GHz or 5GHz | |
Protocol (For wireless Communication): MQTT and MODBUS-TCP | |
Display (Standard) | LCD Display and LED Indicator |
HMI (Standard) | Keypads Programming: Setting of CT/PT Ratio, Communication, Phase Wiring and etc |
Software (Standard) | Adjustment Software: Setting of Data Upload Interval, WiFi configuration (Account&Password), Server Address, Port and etc |
Alarm Function (Standard) | Undervoltage, Overvoltage, Undercurrent, Overcurrent, Underload, Overload, Communication Disconnection and etc |
I/O Function (Optional) | 1-channel DI (Digital Input) 1-channel DO (Digital Output) |
Parameter | Description&Value | ||
Voltage Input | Rated Voltage | 220~264Vac L-N | |
Reference Frequency | 45~65Hz | ||
Power Consumption | <0.5VA (each Phase) | ||
Current Input | Rated Current | 20(100)A AC | |
Starting Current | 1% Ib (Class 0.5); 4% Ib(Class 1) | ||
Power Consumption | <1VA (each Phase) | ||
Phase Wiring | 1P2W | 1-phase 2-wire | |
Measurement Performance | Standard | GB/T17215.322-2008,GB/T17215.321-2008 | |
kWh Accuracy | Class 1 | ||
Pulse | Width of Pulse | 80±20ms | |
Pulse Constant | 1600imp/kWh; |
Condition | Description&Value |
Temperature | Operating Temperature: -25℃~+55℃; Storage Temperature: -40°C ~+70°C |
Humidity | ≤95%RH,no condensation,without corrosive gas |
Altitude | ≤ 2000m |