Acrel ACR10R smart solar energy meter 3 phase popular for Photovoltaic system solutions
Negotiable
Min.Order:1
Function/Model | ACR10RH-DxxT(R)E4 ACR10RH-DxxT(R)E3 | ||
Display mode | LCD(Field LCD) | ■ | |
Measuring parameter | Current/voltage/frequency/power facto | ■ | |
Active power/reactive power/apparent power | ■ | ||
Four quadrant electric energy measurement | ■ | ||
Maximum demand | □ | ||
Multiple rate electric energy measurement | □ | ||
Power quality monitoring | Total harmonic content | ■ | |
subharmonic(2-31 times) | ■ | ||
Data logging | Incident record | □ | |
Display mode | Alarm | □ | |
Built-in clock | □ | ||
Communication | RS485 interface | ■ | |
Optional function (choose one) | J(2DO) | A1+(B1 or C1) (4DI+2DO or 4DI+EP)* |
Technical parameters | Indicators | ||||||
Input | Net work | 3-phase 3-wire,3-phase 4 wire | |||||
Frequency | 45~65Hz | ||||||
Voltage | Rating:AC 57.7V/100V(100V)、220V/380V(400V) | ||||||
Overload:1.2-fold rating(continuous);2-fold rating/1second | |||||||
Consumption:<0.2VA | |||||||
Current | Rating: 80A,120A,200A .etc(See specific product specifications,special parameters can be customized) | ||||||
Overload:1.2-fold rating(continuous);10-fold rating/1 second | |||||||
Consumption:< 0.2VA | |||||||
Output | Electric energy | Output mode:Open-collector photocoupler pulse,two way output | |||||
Three-phase | Pulse constant:4000、8000imp/kWh | ||||||
Communication | RS485 interface,Modbus-RTU Protocol | ||||||
Display mode | LCD | ||||||
Function | Switching | Input | Four way dry contact input | ||||
Output | Output mode: two way relay nO contact output | ||||||
Contact capacity:AC 250V/3A、DC 30V/3A | |||||||
Measuring accuracy | Frequency0.05Hz、reactive electric energy1class、other 0.5class | ||||||
Power supply | AC85~265V or DC100~350V;DC24V(±10%);DC48V(±10%) Consumption≤10VA | ||||||
Safety | Power-frequency withstand voltage | Power frequency withstand voltage between Auxiliary power and switch volume output and current input and voltage input and communication and pulse output and switch volume input terminal is AC2kV 1min;Power frequency withstand voltage between auxiliary power and switch volume output and current input voltage input terminal is AC 2kV/1min;Power frequency withstand voltage between communication and pulse output and switch volume input terminal is AC 1kV/1min; | |||||
Insulation resistance | Input,Output terminal to housing>100MΩ | ||||||
Environment | Working temperature:-10℃~+55℃;Storage temperature:-20℃~+70℃ Relative humidity:5%~95% No condensation;Altitude:≤2500m |