CI871K01 3BSE056797R1 ABB Communication module logic Manager
USD $165 - $260 /Pound
Min.Order:100 Pounds
Xiamen xiongba e-commerce Co., Ltd. Zhangzhou Branch
CI871K01 3BSE056797R1 ABB Communication module logic Manager
CI871K01 3BSE056797R1 ABB Communication module logic Manager
Our Email: 2235954483@qq.com
contact number:13313705507
contacts:HE
Installing the RS-232C Interface, CI853/TP853
CI853 is powered from the processor unit via the CEX bus and requires therefore no
additional external power source.
Use the following procedure to install the CI853/TP853:
1. Mount the unit onto the DIN-rail, see Mounting AC 800M Units onto DIN-Rail
on page 71 and Installing the PM85x/PM86x/TP830 Processor Unit in Single
Configuration on page 84.
2. Connect the cable (maximum 15 m (16.4 yd)) to one of the contacts on the
baseplate. Connect the cable screen to the ground terminal within the connector
to ground the screen via CI583.
3. If cables longer than 15 m (16.4 yd.) are required, then a short distance modem
TC562 must be used. In this case mount the modem onto a DIN-rail in a
suitable position, connect a 24 V DC power supply to the modem and connect
cable TK853 from CI853 to the TC562 modem input terminals
4. Connect the TC562 modem output terminals to the outgoing cable.
The TC562 modem can be used for the following distances/speeds:
• Up to 1000 m (1100 yd) with transmission speed 19200 bit/s
• Up to 12000 m (13100 yd) with transmission speed 1200 bit/s
Connectors
Connect the RS-232C channels to the RJ45 connectors marked COM1 and COM2
on the TP853 Baseplate.