APPLICATION:
Suitable for urban rail transit with rated voltage up to AC 1.8/3kV, railway electrification and DC power transmission of subway lines. Due to its excellent properties, the cable can be suitable for damp, sunlight, anti-termite and anti-rodent environment.
Suitable for fixed installation, outdoor, indoor, direct buried, cable pipes, cable trench, etc.
STANDARD:
GB/T12706, IEC60502, Q/320481SS055-2015, other standards upon request
CONSTRUCTION:
Conductor: fine flexible annealed copper wire, bare or tinned
Separator over conductor(optional)
Insulation: Ethylene-propylene Rubber (EPR)
Inner sheath: LSLH flame-retardant PVC, or LSZH flame-retardant polyolefin
Metallic screen(optional): tinned copper wire braided
Outer sheath: LSLH flame-retardant PVC, LSZH flame-retardant polyolefin
NUMBER OF CORES AND SIZE:
Single core: Copper 10mm2~800mm2
CORE IDENTIFICATION:
Red or white, or as per customer’s requirement
SHEATH COLOR:
black, or as per customer’s requirement
Voltage: DC 700V, DC1000V, DC1500V, AC 1.8/3kV
Continuous conductor temperature at normal operation:90℃
Maximum short-circuit temperature (5 s maximum duration):250℃
Minimum ambient temperature for cable installation:0℃
Minimum bending radius of cable:
-for armored cable: 15D
-for unarmored cable: 20D
SPECIAL FEATURES ON REQUEST:
Flame retardant (IEC60332-1 & IEC60332-3-24, IEC60332-3-23, IEC60332-3-22)
Low smoke and halogen free(IEC61034, IEC60754)
Low smoke and low halogen
Anti-termite and anti-rodent
Use in low temperature
UV resistant/environmental protection requirement
Water-blocking (longitudinal, radial)