EM415-S MID approved din rail mount lcd meter mini digital power meter
Negotiable
Min.Order:1
EM415-S MID approved din rail mount lcd meter mini digital power meter
Main Functions and features:
MID approved single phase kWh meter
Single phase metering power meter
Standard DIN rail Format (DIN43880)
IEC62053-21/22 Class 1.0,0.5S
LCD display, 6 integer 1 decimal
Large clear backlight display
Direct metering up to 100A
Memory back-up (EEprom)
4 DIN modules din rail mount
Performance criteria
Operating humidity ≤ 75%
Storage humidity ≤ 95%
Operating temperature -5°C - +45°C(3K5)
Storage temperature -25°C - +55°C(3K6)
Humanity 75% yearly average,95% on 30 days/year
International standard EN50470-3 &IEC62053-21
Accuracy class CI.1
Protection against penetration of dust and water IP51
Insulating encased meter protective class Ⅱ
Connection area main terminals
Current terminals flexible 1×mm2 0-16mm2
another terminal flexible 1×mm2 0-2.5mm2
Meter specification
Voltage(v) |
230V |
Operational voltage |
±70%Un |
- Iref |
10A |
-Itr |
1A |
-Imax |
100A |
-Imin |
0.5A |
-Ist |
40mA |
Power consumption of current circuits(VA) |
< 0.01 |
Power consumption of voltage circuits(W) |
< 1.3W |
General data |
|
Frequency (Hz) |
50/60 |
Memory back-up |
EEprom |
Environment resistance to heat and fire |
Terminal 960°C Cover 650°C |
upper |
ABS+PC |
lower |
ABS+PC |
Pulse output |
|
Pulse width(ms) |
80 |
Pulse constant(imp/kWh) |
1600 |
LED constant |
1600 |
Width (mm) |
76 |
Height (mm) |
104.5 |
Depth (mm) |
60 |
Pulse output function
Smart meter is equipped with a pulse output which is fully separated from the inside circuit. That generates pulses in proportion to the measured energy .include the testing pulse output of active energy and reactive energy. 14/ 15 Test pulse output contact (P+/P-),13/ 15 Test pulse output contact (Q+/Q-)
The test pulse output is a polarity dependant, passive transistor output requiring an external voltage source for correct operation.
Reading the meter
The smart energy meter is equipped with 6+1 LCD display, which is used as recording consumption and can’t be reset to zero. The number system is based on units of 10. And unit is kWh.