3 Phase Watt Hour Din Rail Mount Voltage Ampere Energy Meter
Negotiable
Min.Order:1
Small Three Phase CT RS485 Smart Electronic Kwh Watt Power Meter
3 Phase 4 Wire Din Rail RS485 Electronic CT Kilowatt Energy Meter
DZS310 Three Phase Bi directional Din Modbus Electronic Kwh Power Meter
Din Rail Three Phase Bidirectional MODBUS RTU Eelectronic Energy Meter
Three Phase Din Modbus Electronic Bi directional Kilowatt Energy Meter
Three Phase Electronic Mobus Energy Kwh Din Rail Power Meter
Technical Parameters-DZS900 | ||||
Accuracy Class | Voltage: 0.2; Current: 0.2; Frequency: 0.05 Hz; Power Factor: 0.5 | |||
Active Power: 0.5; Reactive Power: 0.5; Apparent Power: 0.5 | ||||
Active Energy: 0.5S/1; Reactive Energy: 2 | ||||
Inputs | Rated Value | Voltage: 100 V/400 V Current: 20mA | ||
Overload | Voltage: Sustained Overload: 1.2 times of the rated value Momentary Overload: 2 times of the rated value Current: Sustained Overload: 1.2 times of the rated value Momentary Overload: 10 times of the rated value | |||
Frequency | 45-60Hz | |||
Functional Module | Pulse Outputs | 2 | ||
Interface | 2* RS485; Modbus RTU communication protocol; Baud rate: 1200-19200bps | |||
Power Supply | Working Range | AC: 85-265V; DC: 85-300V | ||
Consumption | < 3W | |||
Working Condition | Temperature | Operating: -20°C~+65°C. Storage: -40°C~ +85°C | ||
Humidity | Relative Humidity: < 93% (place without corrosive gas) | |||
Altitude | <4000m | |||
Dimensions: | 210×100×45mm |