3 phase programmable controller panel pump start delta digital generator engine protector
Negotiable
Min.Order:1
3 phase smart over under voltage protector programmable digital motor start potential relay
KPM83M integrated programmable electronic protector electrical digital motor start potential relay
Programmable three phase digital protection relay motor thermal overload protector for pumps
Panel mounted 3 phase 380V bore motor jacket protection controller
KPM60 - 3 phase digital generator engine protector--Technical parameters | ||||||||
Working power source | Operating Voltage | AC85~265VDC80~300V | ||||||
Rated power | <5VA | |||||||
Input voltage | Rated voltage | 380V-660V | ||||||
Frequency range | 45~65Hz | |||||||
Input current | Rated current | 5A,32A, 100A, 250A, 500A | ||||||
Frequency range | 45~65Hz | |||||||
InputOutput | Switch value input | 8-way passive main line contact DI input, internal supply DC24V power source | ||||||
Relay output | 4-way DO output,Contact capacity 250VAC5A,30VDC5A | |||||||
Analog output | Output range 4~20mA,Programmable | |||||||
Temperature input | Measure range 0℃~100℃ | |||||||
Measurement accuracy | Current | ±1.0%(10%Ie~120%Ie) | ||||||
Leakage current | ±1.0%(5%Ise~100%Ise) | |||||||
Voltage | ±0.5%(20%Ue~150%Ue) | |||||||
Frequency | ±0.02Hz(45Hz~65Hz) | |||||||
Power factor | ±1.0%(-1~1) | |||||||
Energy | ±2.0% | |||||||
Power | ±2.0% | |||||||
Communication | Communication interface | RS485,Photoelectric isolation interface | ||||||
Communication protocol | Modbus-RTU,1200~38400bps Profibus-DP,9600~12Mbps | |||||||
Electrical insulation | Power frequency withstand voltage | AC2kVmin~1mA Input-output-power source | ||||||
Insulation resistance | >50MΩ | |||||||
Impact voltage | 5kV(Peak),1.250us | |||||||
Working environment | Operating temperature | -25℃ ~ +70℃ | ||||||
Relative humidity | 5%~95% No condensation | |||||||
Storage temperature | -30℃ ~ +75℃ |