NC-100H 63A-125A 4P AC 50Hz/60Hz 230V 400V white MCB miniature circuit breaker
Negotiable
Min.Order:1
2. Main Technical Parameter | ||||||||||
Type | DZ47-125/NC-100H | |||||||||
Pole | 4P | 1P,2P,3P | ||||||||
Rated current (A) | 63,80,100,125 | |||||||||
Rated voltage (V) | 230 | 400 | ||||||||
Ambient temperature | -5oC~+40oC | |||||||||
Type of instantaneous release | C,D | |||||||||
Rated short circuit breaking capacity Icn(kA) | 10 |
3. The over-current protection property | ||||||||||
Ambient Temperature | Initial Status | Test Current | Expected Result | Expected Result | NOte | |||||
40±2oC | Cold position | 1.05In(In≤63A) | t≥1h | Non-release | - | |||||
Cold position | 1.05In (In>63A) | t≥2h | Non-release | - | ||||||
Carried out immedi-ately after previous test | 1.30In(In≤63A) | t < 1h | Release | Current smoothlyrises to specified value within 5s | ||||||
1.30In (In>63A) | t < 2h | Release | ||||||||
-5~+40oC | Cold position | 8.00In | t≤0.2s | Non-release | - | |||||
Cold position | 12.00In | t< 0.2s | Non-release | - |
4. Applicable conducting wire | ||||||||||
Rated current(A) | Nominal cross section of wire mm2 | |||||||||
63A | 16 | |||||||||
80A | 25 | |||||||||
100A | 35 |