11kv 27kv 38kv pole mounted vacuum auto recloser controller unit ftu
Negotiable
Min.Order:1
Vacuum circuit breaker recloser controller protective relay senses faults and clear the fault
Outdoor three phase intelligent recloser controller unit ct pt and disconnector
Pole mounted auto vacuum circuit breaker sectionalizer switch 11kv 630a recloser controller
33kv 36kv outdoor vacuum circuit breaker overhead power line auto recloser with controller
High voltage outdoor pole mounted auto circuit recloser controller ct pt disconnector & controller
Description
Recloser controls are the front line of the distribution power system, often located on feeders or in distribution substations. Recloser controls supply the intelligence to the network and handle the network protection and in many cases even the RTU functionality. The protective relay senses the faults, assists the vacuum circuit breaker module in an auto recloser to clear the fault on the line.minimize outage duration and the numbers of customers affected by faults.
Application
Advantages
1. Fault clearance functionality and RTU functionality.
2. Status monitoring – local and remote.
3. Configuration and Control – local and remote (complete).
4. Power quality monitoring – local and remote.
5. Event recorder for fault analysis.
6. Metering – local and remote.
7. Multi signalling protocol - IEC 870-5-101, IEC 870-5-104,IEC 61850 and IEC 60870-5-101 and DNP.
8. The operator panel module which provides the Human Machine Interface.
Technical Parameters
No. |
Item |
Unit |
Parameter |
1 |
Rated voltage |
kV |
12 |
2 |
Rated current |
A |
630 |
3 |
Lightning impulse withstand voltage (peak) phase to phase, to ground/fracture |
kV |
75/85 |
4 |
Rated short-circuit breaking current |
kA |
20 |
5 |
Rated short-circuit making current (peak value) |
kA |
50/63 |
6 |
Rated peak withstand current |
kA |
50/63 |
7 |
4s short-time withstand current |
kA |
25 |
8 |
Rated short-circuit current breaking times |
number |
30 |
9 |
Mechanical life |
number |
10000 |
10 |
Rated voltage of energy storage motor |
V |
DC24 |
11 |
Rated power of energy storage motor |
W |
70 |
12 |
Rated operating voltage |
V |
DC24 |
13 |
Energy storage time under rated voltage |
s |
<10 |
14 |
Partial release of the whole machine |
pC |
<10 |
Related products