Over under voltage protection 40A 63A 220V auto voltage protector voltage monitor current protector
Negotiable
Min.Order:1
The automatic recovery over voltage and under voltage protective device complies with modular design standards. the circuit boards of products adopt good quality electronic components with reliable performance. when the power situation is unstable. It's protection function will be automatically activated. once the voltage exceeds the limited range of products, it will automatically cut off so as to protect the safely of electrical equipment and persons. The device will re-supply in 1 minute, when the power returns to normal.
The green indicator display, when the power is normal supply.
The red indicator display, when the power over voltage or under voltage.
Installing: 35mm Din rail.
Main Technical Speacification OF 40A
Rated | AC voltage 230V±10% and frequency 50Hz/60Hz |
Passing Max Current | 40A |
Max. Loading power | 8.8KVA |
Over-voltage action cut-off value | >275VAC+/-5V |
Normal-voltage value | 165-275VAC |
Under-voltage action cut-off value | <160VAC+/-5V |
Over voltage and under voltage cut-off | < 1s |
Electricity transmitting delay after cut-off | <60s |
Self power consumption | <2W |
Electric machinery life | =100000 times |
Dimension | 35L*70W*77Hmm |
Installing | 35mm Din rail |
Main Technical Speacification OF 60A
Rated | AC voltage 230V±10% and frequency 50Hz/60Hz |
Passing Max Current | 63A |
Max. Loading power | 13.8KVA |
Over-voltage action cut-off value | >275VAC+/-5V |
Normal-voltage value | 165-275VAC |
Under-voltage action cut-off value | <160VAC+/-5V |
Over voltage and under voltage cut-off | < 1s |
Electricity transmitting delay after cut-off | <60s |
Self power consumption | <2W |
Electric machinery life | =100000 times |
Dimension | 35W*66L*84Hmm |
Installing | 35mm Din rail |
Noted: When you first connect the product, you have to wait about 1 minute, after the red light turn off, then the product will work.