LNF56 96*96mm RTM measurement LCD panel mounted 3 phase smart energy meter
Negotiable
Min.Order:1
Jiangsu Sfere Electric Co., Ltd.
LNF66 smart electricity meter electrical measurements modbus energy meter
LNF32 0~6A LCD panel single 1 phase AC electric current meter
LNF56 RTM measurement digital LCD panel mounted m-bus energy meter
LNF56 rtm real time measurement home energy monitor energy meter
LNF56 96*96mm RS485 3 phase digital power bidirectional smart energy meter
PD194Z-9S4 96*96mm 3 phase digital bidirectional kwh meter with modbus
LNF53 | LNF56 | ||
Real-time measurement | U/I/P/Q/S/PF/F | - | - |
Demand | - | - | |
Energy metering | Bi-directional energy | - | - |
Four-quadrant reactive energy | - | - | |
Power quality | Sequence component and phase position of voltage and current | - | - |
Voltage and current unbalance | - | - | |
Input and output | Input and output | - | - |
RS485 communication interface | - | - | |
Appearance dimension | Display mode | LCD | LCD |
Panel size(mm) | 72×72 | 96×96 |
Working environment | ||
Working temperature | -10°C -- 55°C | |
Storage temperature | -25°C -- 70°C | |
Relative humidity | ≤95% RH, no condensation | |
Working altitude | ≤2500m | |
Anti-pollution level | Non-corrosive gas | |
Protection degree | Front case IP54, rear case IP20. | |
Insulation | Between signal, power supply, output terminal to case resistance >100MΩ | |
Withstand voltage | Input and power supply ≥ 2kV, input and output ≥ 2kV, power supply and output ≥ 2kV | |
Display | ||
Display method | LCD | |
Working power supply | ||
Rated range | AC/DC(80~270)V | |
Power consumption | ≤5VA | |
Withstand voltage | ≥2kV | |
Voltage input | ||
Range | 3×230/400V | |
Resolution | 0.1 V | |
Impedance | ≥1.7 MΩ/ per phase | |
Power consumption | ≤0.1 VA / per phase | |
Overload | Continuous:1.2Vn Instantaneous:2Vn/1min | |
Frequency | 45 Hz-65 Hz | |
Current input | ||
Range | 3×5A/1A | |
Resolution | 1mA | |
Impedance | ≤20mΩ/ per phase | |
Power consumption | ≤0.2 VA/ per phase | |
Overload | Continuous:1.2Vn Instantaneous:10In/5s | |
Energy pulse output | ||
Pulse width | 80ms±20% | |
Max. terminal voltage | 35V | |
Max. terminal current | 10mA | |
Pulse frequency | ≤10Hz | |
Output object | Import active energy, import reactive energy | |
Communication interface | ||
Physical interface | RS-485 | |
Communication speed | Up to 9.6 kbps | |
Communication protocol | Modbus-RTU | |
Isolation voltage | 2000 VAC (1 min) |