S11 Series 6kV-35kV power Transformer With Off Circuit Tap Changer
Negotiable /Piece
Min.Order:1 Piece
Baoding Zhongyi Electrical Material Manufacturing Co.,Ltd.
Proudct description
The products comply with the national standard GB1094-2013 power transformer and GB/T6451-2015 "Three-phase Oil-immersed Power Transformer Technical Parameters and Requirements", and are recommended as the key equipment products of national urban and rural power grid construction and transformation by The State Grid Corporation of China. State Economic and Trade Commission.
S11 series transformer adopts high quality copper winding materials, especially coil insulation and active parts adopt new technology, new materials, no-load loss and load loss are significantly reduced, performance and structure more reliable and superior.
Proudct features
● Good economic benefits
The no-load loss of S11 series products decreased by 10.3% on average, and the no-load current decreased by 22.4% compared with S9 series.
● Long service life
Transformer oil tank adopts closed structure, oil tank and oil tank cover can be bolted or welded firmly, transformer oil will not contact with air, effectively prolong the service life.
● High operation reliability
Improve the sealing parts of the tank, improve the reliability, improve the technical level, to ensure the reliability of the seal.
● Small installation area
S11-m series transformer tank adopts corrugated plate radiator. When the oil temperature changes, corrugated plate will be thermal expansion, can replace the role of oil storage tank. Corrugated plate tank beautiful appearance, small footprint.
Model and Meaning
Table 1: 6Kv, 10kV & 30kVA-2500kVA Power Transformer With Off Circuit Tap Changer
Rated Capacity (kVA) | Voltage Combination | Connection Group Symbol | No-load Loss R(W) | Load Loss R(W)75℃ | Impedance Voltage (%) | No-load Current(%) | Length L(mm) | Width W (mm) | Height H(mm) | Gauge Horizontal*Vertical(mm) | Active parts Weight(Kg) | Oil Weight(Kg) | Total Weight(Kg) | ||
(KV) High Voltage | Tapping Range of High Voltage | (KV)Low Voltage | |||||||||||||
30 | 66.31010.5 | ±5%±2×2.5% | 0.4 | Dyn11Yzn11Yyn0 | 100 | 630/600 | 4.0 | 2.8 | 980 | 735 | 1145 | 400*400 | 178 | 78 | 355 |
50 | 130 | 910/870 | 2.5 | 1017 | 758 | 1205 | 450*400 | 240 | 92 | 415 | |||||
63 | 150 | 1090/1040 | 2.4 | 1035 | 785 | 1285 | 450*400 | 285 | 105 | 505 | |||||
80 | 180 | 1310/1250 | 2.2 | 1065 | 800 | 1290 | 450*400 | 330 | 110 | 540 | |||||
100 | 200 | 1580/1500 | 2.1 | 1072 | 820 | 1305 | 450*400 | 345 | 116 | 590 | |||||
125 | 240 | 1890/1800 | 2.0 | 1155 | 1105 | 1310 | 450*550 | 415 | 135 | 705 | |||||
160 | 280 | 2310/2200 | 1.9 | 1235 | 850 | 1535 | 550*550 | 485 | 155 | 835 | |||||
200 | 340 | 2730/2600 | 1.8 | 1282 | 860 | 1557 | 550*550 | 582 | 168 | 965 | |||||
250 | 400 | 3200/3050 | 1.7 | 1310 | 940 | 1605 | 550*550 | 695 | 210 | 1135 | |||||
315 | 480 | 3830/3650 | 1.6 | 1465 | 1120 | 1915 | 660*650 | 855 | 255 | 1520 | |||||
400 | 570 | 4520/4300 | 1.5 | 1440 | 1165 | 1725 | 660*660 | 950 | 295 | 1590 | |||||
500 | 680 | 5410/5150 | 1.4 | 1510 | 1250 | 1845 | 660*650 | 1150 | 320 | 1905 | |||||
630 | 810 | 6200 | 1.3 | 1650 | 1140 | 1920 | 660*650 | 1500 | 435 | 2015 | |||||
800 | 980 | 7500 | 4.5 | 1.2 | 2125 | 1175 | 2315 | 820*820 | 1910 | 760 | 3510 | ||||
1000 | 1150 | 10300 | 1.1 | 2150 | 1380 | 2570 | 820*820 | 2125 | 880 | 3850 | |||||
1250 | 1360 | 12000 | 1.0 | 2355 | 1485 | 2570 | 820*820 | 2605 | 960 | 4610 | |||||
1600 | 1640 | 14500 | 0.9 | 2385 | 1750 | 2630 | 820*820 | 3125 | 1150 | 5420 | |||||
2000 | 1940 | 18300 | 5.0 | 0.4 | 1940 | 1400 | 1700 | 820*820 | 2420 | 780 | 4200 | ||||
2500 | 2290 | 21200 | 0.4 | 2050 | 1480 | 1800 | 820*820 | 2560 | 880 | 4680 |
Notes:
1. The Dimension and weight will be changed according to the requirements. These two data in the table will be subject to the factory documents.
2. For the transformer of rated capacity up to 500kVA, the value of load loss above the oblique line in the table is applicable to the connection group Dyn11 or Yzn11. The value of load loss under the oblique line is applicable to the connection group Yyn0.
Technical Parameter for S11 Series 20kV Power Transformer With Off Circuit Tap Changer
Rated capacity(KVA) | Voltage Combination | Connection Group Symbol | No-load Loss(W) | Load Loss (W)75℃ | No-load Current (%) | Short-circuit Impedance(%) | ||
High Voltage (KV) | Tapping ranges of High Voltage | Low Voltage(KV) | ||||||
30 | 20 | ±5% ±2×2.5% | 0.4 | Dyn11Yzn11Yyn0 | 100 | 690/660 | 2.1 | 5.5 |
50 | 130 | 1010/960 | 2.0 | |||||
63 | 150 | 1200/1150 | 1.9 | |||||
80 | 180 | 1440/1370 | 1.8 | |||||
100 | 200 | 1730/1650 | 1.6 | |||||
125 | 240 | 2080/1980 | 1.5 | |||||
160 | 290 | 2540/2420 | 1.4 | |||||
200 | 340 | 3000/2860 | 1.3 | |||||
250 | 400 | 3520/3350 | 1.2 | |||||
315 | 480 | 4210/4010 | 1.1 | |||||
400 | 570 | 4970/4730 | 1.0 | |||||
500 | 680 | 5940/5660 | 1.0 | |||||
630 | 810 | 6820 | 0.9 | 6.0 | ||||
800 | 980 | 8250 | 0.8 | |||||
1000 | 1150 | 11330 | 0.7 | |||||
1250 | 1380 | 13200 | 0.7 | |||||
1600 | 1660 | 15950 | 0.6 | |||||
2000 | 1950 | 19140 | 0.6 | |||||
2500 | 2340 | 22220 | 0.5 |
Notes:
1. The Dimension and weight will be changed according to the requirements. These two data in the table will be subject to the factory documents.
2. For the transformer of rated capacity up to 500kVA, the value of load loss above the oblique line in the table is applicable to the connection group Dyn11 or Yzn11. The value of load loss under the oblique line is applicable to the connection group Yyn0.
3. The performance parameters in the table are also applicable for HV with dual voltage 20 (10)kV three-phase transformer.
Technical Parameter for S11 Series 35kV Power Transformer With Off Circuit Tap Changer
Model | Voltage Combination | Connection Group Symbol | No-load Loss (W)75℃ | Load Loss R(W) | Impedance Voltage (%) | No-load Current(%) | Length L(mm) | Width W(mm) | Height H(mm) | Gauge Horizontal*Vertical (mm) | Active parts Weight(Kg) | Oil Weight(Kg) | Total Weight(Kg) | ||
High Voltage (kV) | Tapping Range of High Voltage % | Low Voltage (kV) | |||||||||||||
50 | 3538.5 | ±2×2.5%±5% | 0.4 | Dyn11/ Yyn0 | 160 | 1200/1140 | 6.5 | 1.3 | 1195 | 935 | 1825 | 660*660 | 300 | 330 | 860 |
100 | 230 | 2010/1910 | 1.1 | 1200 | 995 | 1935 | 660*660 | 470 | 383 | 1130 | |||||
125 | 270 | 2370/2260 | 1.1 | 1235 | 940 | 1955 | 660*660 | 550 | 465 | 1335 | |||||
160 | 280 | 2820/2680 | 1.0 | 1285 | 895 | 1950 | 660*660 | 580 | 485 | 1475 | |||||
200 | 340 | 3320/3160 | 1.0 | 1310 | 1150 | 1985 | 660*660 | 680 | 595 | 1755 | |||||
250 | 400 | 3950/3760 | 0.95 | 1450 | 1090 | 2010 | 660*660 | 860 | 650 | 2000 | |||||
315 | 480 | 4750/4530 | 0.95 | 1930 | 1065 | 2320 | 820*820 | 980 | 765 | 2290 | |||||
400 | 580 | 5740/5470 | 0.85 | 1850 | 1165 | 2015 | 820*820 | 1170 | 885 | 2725 | |||||
500 | 680 | 6910/6580 | 0.85 | 2045 | 1205 | 2415 | 820*820 | 1340 | 960 | 3090 | |||||
630 | 830 | 7860 | 0.65 | 2085 | 1240 | 2515 | 660*660 | 1550 | 895 | 3810 | |||||
800 | 980 | 9400 | 0.65 | 2305 | 1615 | 2685 | 820*820 | 1990 | 1030 | 4510 | |||||
1000 | 1150 | 11500 | 0.65 | 2545 | 1540 | 2590 | 1070*1070 | 2415 | 1475 | 5055 | |||||
1250 | 1400 | 13900 | 0.60 | 2495 | 2010 | 2675 | 820*820 | 2480 | 1405 | 5290 | |||||
1600 | 1690 | 16600 | 0.60 | 2680 | 2100 | 2770 | 820*820 | 2600 | 1490 | 5450 | |||||
2000 | 1990 | 19700 | 0.55 | 2790 | 2180 | 2860 | 820*820 | 2720 | 1590 | 5600 | |||||
2500 | 2360 | 23200 | 0.55 | 2900 | 2290 | 2980 | 1070*1070 | 2830 | 1720 | 5760 |
Notes:
1. The Dimension and weight will be changed according to the requirements. These two data in the table will be subject to the factory documents.
2. For the transformer of rated capacity up to 500KVA, the value of load loss above the oblique line in the table is applicable to the connection group Dyn11. The value of load loss under the oblique line is applicable to the connection group Yyn0.
S11 Series 35kV 630kVA-31500kVA Three-phase Dual Winding Power Transformer With Off Circuit Tap Changer
Model | Voltage Combination | Connection Group Symbol | No-load Loss (W) | Load Loss R(W) | No-load Current(%) | Short circuit impedance (%) | Length L(mm) | Width W(mm) | Height H(mm) | Gauge Horizontal*Vertical (mm) | Active parts Weight(Kg) | Oil Weight(Kg) | Total Weight(Kg) | ||
High Voltage (kV) | Tapping Range of High Voltage % | Low Voltage (kV) | |||||||||||||
630 | 35 | ±2×2.5%±5% | 3.156.310.5 | Yd11 | 830 | 7860 | 0.65 | 6.5 | 2400 | 1700 | 2210 | 820*820 | 2210 | 900 | 3250 |
800 | 980 | 9400 | 0.65 | 2500 | 1850 | 2390 | 820*820 | 2350 | 1030 | 3500 | |||||
1000 | 1150 | 1150 | 0.65 | 2700 | 1950 | 2510 | 820*820 | 2490 | 1180 | 3860 | |||||
1250 | 1400 | 1390 | 0.55 | 2900 | 2050 | 2630 | 820*820 | 2600 | 1350 | 4350 | |||||
1600 | 1690 | 1660 | 0.45 | 3050 | 2130 | 2750 | 820*820 | 2810 | 1580 | 4855 | |||||
2000 | 2170 | 1830 | 0.45 | 3105 | 2195 | 2805 | 1070*1070 | 2800 | 1800 | 5300 | |||||
2500 | 2560 | 1960 | 0.45 | 3150 | 2535 | 2980 | 1070*1070 | 3525 | 2060 | 7665 | |||||
3150 | 35-38.5 | ±2×2.5%±5% | 3.156.310.5 | 3040 | 2300 | 0.45 | 7.0 | 3920 | 2725 | 2840 | 1070*1070 | 3995 | 2205 | 8565 | |
4000 | 3610 | 2730 | 0.45 | 3310 | 2915 | 3070 | 1070*1070 | 4825 | 2560 | 10115 | |||||
5000 | 4320 | 3130 | 0.45 | 3480 | 3020 | 3145 | 1070*1070 | 5700 | 2635 | 11305 | |||||
6300 | 5240 | 3500 | 0.45 | 8.0 | 3590 | 2905 | 3210 | 1475*1475 | 7120 | 3240 | 13510 | ||||
8000 | 35-38.5 | ±2×2.5% | 3.153.36.36.610.5 | YNd11 | 7200 | 3840 | 0.35 | 4070 | 3050 | 3595 | 1475*1475 | 8875 | 3840 | 16690 | |
10000 | 8700 | 4530 | 0.35 | 4106 | 2795 | 3655 | 2000*1475 | 10305 | 3600 | 17690 | |||||
12500 | 1000 | 5380 | 0.30 | 4570 | 3010 | 3840 | 1475*1475 | 12830 | 4310 | 20990 | |||||
16000 | 1210 | 6580 | 0.30 | 5235 | 3295 | 4615 | 2000*1475 | 16010 | 6650 | 27660 | |||||
20000 | 1440 | 7950 | 0.30 | 5360 | 3415 | 4660 | 2000*1475 | 18820 | 7600 | 32170 | |||||
25000 | 1700 | 9400 | 0.25 | 10.0 | 5830 | 3810 | 4860 | 2000*1475 | 22360 | 9800 | 42600 | ||||
31500 | 2020 | 112000 | 0.25 | 6290 | 4290 | 5260 | 2000*1475 | 25110 | 12010 | 49960 |
Note: 1.For the transformer of low voltage 10.5kV, the connection group symbol is applicable to Dyn11.
Note: 2.For the transformer of rated capacity 3150kVA or above, the -5% tapping position is for maximum current tap.
Note: 3.When the annual average load rate for the transformer is between 35% to 45%, the loss value in the table can obtain the highest operational efficiency.