TK3205 250v To 10kv Digital Insulation Resistance Tester Meter Meg
Negotiable /Piece
Min.Order:1 Piece
Wuhan Guodian Mingke Electric Co., Ltd.
It is suitable for evaluating the insulation quality of high voltage transformergenenratorling-distance power cable and busbar under strong interference in the field of high-voltage substation and power plant.Specially used for 110KV and above large capacity transformer and long distance power cable power system
1.Strict accordance with the safety standards for design with 5 range: 500V 1000V 2500V 5000V 10000V test up to 10TΩ.
2.This instrument has the function of automatic calibration and calibrate precision automatly before test
3.Actual test object live voltage measurement functionmeasure leakage currentdischarge automatly.
4.automatic measure and remenber R15S、R60S 、R10min valueAutomatic display polarization index (PI) induced electric absorption test values than (DAR)and test time.
5.Anti-jamming performance is superior the interference current reaches 600 mA still ensure accuracy of test instruments.
6.Automatic discharge:quickly discharge for capacitive test object by advanced high-voltage discharge technology and real-time measurement of discharge voltage (test voltage to 0v) .
7.powered by internal rechargeable lithium battery or ac power supply the real ac and dc dual use does not affect the test accuracy.
8.digital displayautomatic display battery level and undervoltage alarm protection function.
9.Short circuit protection short circuit condition will not burn out the instrument
insulation resistance | 50MW | withstand | AC 10kV 50Hz 1min |
working temperature humidity | -30℃ ~ +60℃ 85%RH | ||
charge power | 220V±10%,50/60 HZ | battery power | Two batteries supply power at the same time 16.8V lithium ion rechargeable battery 2600mAH7.4v 2200mAH |
display | Digital and analog pointer dual display | screen | 5.7inch resolution320*240 |
Insulation resistance measurement range and accuracy | |||
rated voltage(kV) | 0.250.5,1,2.5,5 | 0.51,2.5,5,10 | |
measurement voltage(kV) | rated voltage ×(1±10%) The load resistance shall not be lower than the range 1% | ||
The min error is within the range of 5%RDG | (0.001~100)GW/5kV (0.001~200)GW/2.5kV (0.001~50)GW/1kV (0.001~20)GW/0.5kV (0.001~5)GW/0.25kV | (0.001~100)GW/10kV (0.001~200)GW/5kV (0.001~200)GW/2.5kV (0.001~100)GW/1kV (0.001~20)GW/0.5kV | |
The max error is within the range of 10%RDG | (100~200)GW/5kV (5~10)GW/0.25kV | (100~200)GW/10kV (100~200)GW/5kV | |
The max error is within the range of 20%RDG | (200~1000)GW/5kV (200~500)GW/2.5kV (100~200)GW/1kV | (200~1000)GW/10kV (200~1000)GW/5kV (200~500)GW/2.5kV (100~200)GW/1kV | |
output short-current | ≥8mA | ≥8mA | |
measurement rang of absorptance and PI | measurement rang: 0.01 ~99.99 max error: ±(1%RDG+1d) | measurement rang: 0.01 ~99.99 max error: ±(1%RDG+1d) | |
Output voltage display error | ±(3%RDG + 1d) | ±(3%RDG + 1d) |