TOP Supplier NYY Power Cable (NYY-O NYY-J) 0.6/1kV
Negotiable
Min.Order:1
Zhengzhou Aobest Electronic Technology Co., Ltd.
1, rated voltage : 0.6/1kv
2, conductor working temperature: no more than 90°C.
3, model and name look following table.
Cu Core | AL Core | Description | Main application |
VV
ZR-VV | VLV
ZR-VLV
| Cu(Al)Core PVC Insulated PVC Sheathed Power Cable Cu(Al)Core PVC Insulated PVC Sheathed Fire Resistant power Cable | For laying in doors, inducts and in tunnels, but unable to bear pulling force and pressure.
|
VV22
ZR-VV22 | VLV22
ZR-VLV22 | Cu(Al)Core PVC Insulated Steel Tape Armored PVC Sheathed Power Cable u(Al)Core PVC Insulated Steel Tape Armored PVC Sheathed flame retardant Power Cable | For laying indoor, inducts, tunnels and direct in ground, able to bear pulling force and pressure.
|
VV32
ZR-VV32 | VLV32
ZR-VLV32 | Cu(Al)Core PVC Insulated thin Steel Wire Armored PVC Sheathed Power Cable Cu(Al)Core PVC Insulated thin Steel Wire Armored PVC Sheathed flame retardant Power Cable | For laying down indoor, wells and under water, able to bear certain axis pulling force.
|
VV42
ZR-VV42 | VLV42
ZR-VLV42 | Cu(Al)Core PVC Insulated Thick Steel Wire Armored PVC Sheathed Power Cable
Cu(Al)Core PVC Insulated Thick Steel Wire Armored PVC Sheathed flame retardant Power Cable |
For laying down wells and under water, able to bear certain pulling force.
|
4, conductor : copper conductor, aluminum conductor.
5, insulation material : PVC insulated, XLPE insulated, PE insulated.
6, PVC sheathed, with steel tape armored, with steel wire armored,
Flame retardant models can be divided into ZA, ZB, ZC that represent flame-retardant class of A, B, and C respectively.
7, pls provide the detailed cable or wire information as below,
(1), VV, VLV, ZR-VV,ZR-VLV
0.6/1kv, PVC insulated PVC sheathed flame retardant and non-flame retardant power cable
VV, VLV, ZRVV,ZRVLV have different cores, 3 cores, 4 cores, 5 cores, 3+1 cores, 3+2 cores, 4+1 cores
VV, VLV, ZR-VV,ZR-VLV | |||||||
No. of Core | Nom. cross Section Area(mm2) | Single quantity of conductor | Insu. Thick (mm) | Sheath thick (mm) | Approx. dia. Of cable (mm) | D.C resistant((Ω/km) Cu Al | |
1 | 1.5~800 | 1~61 | 0.8~2.9 | 1.4~2.4 | 6.1~46.1 | 12.1~0.221 | 0~0.0367 |
2 | 1.5~400 | 1~61 | 0.8~2.6 | 1.8~2.8 | 10.5~56.0 | 119~8356 | 100~3320 |
3 | 1.5~400 | 1~61 | 0.8~2.6 | 1.8~3.0 | 10.9~60.6 | 142.0~12103.0 | 113.0~4869.0 |
4 | 2.5~400 | 1~61 | 0.8~2.6 | 1.8~3.2 | 12.7~70.0 | 232.0~16788 | 169~6708 |
5 | 2.5~400 | 1~61 | 0.8~2.6 | 1.8~3.6 | 13.6~87.0 | 272~21164 | 193~8564 |
3+1 | 4~400, 2.5~240 | 1~37 1~61 | 1.0~2.6 0.8~1.6 | 1.8~3.3 | 14.3~66.0 | 254~14562 | 211~5968 |
3+2 | 4~400, 2.5~240 | 1~61 1~37 | 1~2.6 0.8~1.6 | 1.8~3.3 | 15.2~78.2 | 345~18250 | 238~7666 |
4+1 | 4~400, 2.5~240 | 1~61 1~37 | 1~2.6 0.8~1.6 | 1.8~3.4 | 15.6~79.1 | 358~19928 | 251~8366 |
8, VV22, VLV22, ZRVV22, ZRVLV22: 0.6/1kv, PVC insulated steel armored PVC sheathed flame retardant and non-flame retardant power cable, has1 core, 2 cores, 3 cores, 4 cores, 5 cores, 3+1 cores, 3+2 cores, 4+1 cores.
More info. will be offered, if needed.