Multifunction Three Phase RS485 Multi-loop Power Meter AMC16MA
Negotiable /Piece
Min.Order:1 Piece
AEW100 Remote Wireless Electricity Monitoring Meter Three Phase
Digital Electricity AMC72L-AI3 AC Ammeter Meter with Modbus-RTU
BD-3I3 Three Phase AC Current Electricity Transducer Analog Output
AM4-I Undervoltage Alarm Medium Voltage Motor Protection Device
ARD2-25 LED Display Blocking Motor Protector For Motor Power
AMC16 series multi circuit monitoring device is a measuring device designed specifically for the power supply management of server in the data center.
Such device is small and exquisite in design, capable of centralized monitoring on various electric parameters and on-off states of dozens of
circuits,including incoming line circuit and outgoing line circuit, and it achieves the highly integration of monitoring circuits in volume.
Charactristics
Product Features
Monitoring Up to 12 Three-phase Circuits or 36 circuits Single phase
Measuring incoming main line 3 phase voltage
Incoming line: 2 channel 3 phase I,Kw,Kvar,cosφ,Kwh(current, active power, reactive power, power factor, active energy, reactive energy)
Outgoing line: 36 channel single phase (12 channel 3phase)I,Kw,Kvar,cosφ,Kwh,Kvarh(need to allocate AHK-0.66W 100A/20mA CTs
Inbuilt communication:1 channel RS485
1 DO, Power supply:AC 220V
Optional functions:
1.RS485/Modbus
2.DC48V power supply
Dimensions and Wirings
Wiring
Datasheet
Input circuits | |
Measuring incoming main line 3 phase voltage | |
incoming line: 2 channel 3 phase I,Kw,Kvar,cosφ,Kwh(current, active power, reactive power, power factor, active energy, reactive energy) | |
Rated input voltage: | AC220V |
Measurement range: | AC 40~400V |
Overload: | instantaneous voltage twice/30 seconds |
rated input current: | inlet:5A outlet:20mA |
measurement range: | inlet:5-10000A outlet:0.25-125A |
Overload: | sustained voltage1.2times,instantaneous current 10times/5 seconds |
Output circuits | |
outgoing line: 36 channel single phase (12 channel 3phase) I,Kw,Kvar,cosφ,Kwh,Kvarh(need to allocate AHK-0.66W 100A/20mA CTs) | |
Frequency | |
45-60HZ | |
Auxiliary power supply | |
AC80-270V or DC100V-350V/DC48V±20% | |
Accuracy | |
class 0.5(current,voltage ) ; class 1(power,energy) | |
Relay output | |
5A/250VAC or 5A/30VDC | |
Communication | |
RS485 ModBus-RTU protocol | |
Functions | |
1 DO, aux. power supply:AC 220V | |
Optional functions | |
2*RS485 ModBus-RTU protocol | |
DC 48V power supply | |
Installation | |
Din rail 35mm |