Electric valve actuator explosion-proof type fry-ex05 fry-ex10 fry-ex15 fry-ex20
USD $600 - $1300 /Piece
Min.Order:1 Piece
TIANJIN FREYA AUTOMATION TECHNOLOGY CO., LTD
ELECTRIC ACTUATOR MODEL : SMB-RS600/F40 HT 380 VOLT AC - 3 FASE 0,65 KW
QUARTER - TURN VALVE ELECTRIC ACTUATOR ; MANU. TIANJIN; TYPE:DY-J41
Motorized with electric Rotary valve actuators bqt15-0.7 bqt19-0.7 bqt28-0.6 bqt38-0.6
1/4turn or part turn 90 degree electric actuator bqt50-0.6 bqt60-0.5 bqt80-0.5
Motorize Automatic Actuator SKJ2100 SKJ 3100 SKJ 4100 SKJ 5100
What is Anti-Explosion?
Explosion can be prevented if anyone condition of three conditions above-mentioned is restricted to happen. In many working sites, explosive material and oxygen are difficult to avoid, so the ignition source should be restricted.
The electric equipment is a potential ignition source, this result in a elevatory surface temperature, ESD or a electric spark caused by transient current, etc. when the machine is turning.
The anti-explosion electric equipment doesn’t become potential ignition source. because it avoids elevatory surface temperature and electric spark caused by the current in the process in the design.
Electric equipment used in explosive gas atmosphere is usually divided into two categories:
I. electric equipment designed for colliery;
II. electric equipment designed for other explosive gas atmospheres except for colliery.
For electric equipment II, it can be divided into three magnitudes of explosion of II A, II B, II C according to MESG (Exd) and minimum experimental ignition current (intrinsic safety type) of detonating gas. and the equipment II B is suitable for service conditions of equipment II A, the equipment II C is suitable for service conditions of equipment II A and II B.
For electric equipment ll, it can be divided into six temperature groups of T1 (450°C) , T2 (300°C) , T3 (200°C) , T4 (135°C) , T5 (100°C) , T6 (85°C) according to allowable maximum surface temperature, and the equipment of higher temperature group is suitable for service conditions of lower temperature group.
More than 90% explosive gas are included in magnitudes of explosion of II A, II B and temperature groups of T1-T4.
Temperature group | |||||||
T1 (450°C) | T2 (300°C) | T3 (200°C) | T4 (135°C) | T5 (100°C) | T6 (85°C) | ||
Magnitude of explosive | IIA | Acetone, ethane, ammonia, benzene, acetic acid, carbinol, propane methylbenzene… | Alcohol, butane butanol, ethene, dichloro ethane … | Benzene, diesel oil, aviation gasoline, ethane, fuel … | Aldehyde | ||
IIB | Gas | Ethene | Ether | ||||
IIC | Hydrogen | Ethyne | Carbon, Disulfide |
Shipment Term:
1. Orders processed timely after the payment verification .
2. Terms of Deliver: FOB / CFR / CIF / EXW etc.
3. Due to stock status and time differences , we will choose to ship your item from our first available warehouse for fast delivery .
Payment Term:
1. Accept T/T, D/A, D/P, L/C, West Union with 30% Deposit.
2. Advance payment should be made within 3 days of order .
Our company provides you with the following services free of charge:
1. All-round electric actuator and valve technology selection service
2. High-quality post-product maintenance and technical analysis services
3. Accept other related cooperation.