Three phase voltage, Zero sequence voltage Three phase current, Zero sequence current Three phase active power, Total active power Three phase reactive power, Total reactive power Three phase apparent power, Total apparent power Three phase Power factor, Total power factor Frequency, Voltage phase angle, Voltage and current imbalance,Forward and reverse power Four quadrant energy metering,System time display 1 channel RS485 interface / Modbus-RTU protocol and the statute DLT645. | ①2DI+2DO+1Ep(K) ②4DI+2DO(K) ③Event record (SOE) ④Total harmonic measurement (H) | ①③④
②③④
| |
①4DI+2DO+1Ep(K) ②2DI+2DO+1Ep(K) ③Event record (SOE) ④2-31th harmonic measurement (H) ⑤2-channel analog output (M) | ①③④
②③④⑤
| ||
AMC96-E4/KC AMC96L-E4/KC | |||
AMC72-E/KC AMC72L-E/KC | single-phase voltage,single-phase current active power, reactive power, apparent power Power factor Frequency Four quadrant energy metering,System time display 1 channel RS485 interface / Modbus-RTU protocol and the statute DLT645. | ①2DI+2DO+1Ep(K) ②4DI+2DO(K)
|
Note:
1.DI--Switching input, DO--Switching output, M--Analog output, SOE--Event recording, H--Harmonic measurement, Ep--Electric energy pulse
2.When the digital tube is displayed, the harmonic data is not displayed, and the data is read only by communication.
3.K is a required function,Choose from ①②
4.When Event record (SOE) is selected,Extreme value and maximum demand(D)are available at the same time.
Technical Parameters
Technical parameters | Value | ||||
Input | Connection | Single phase-2-wire, 3-phase-3-wire, 3-phase-4-wire | |||
Frequency | 45-65Hz | ||||
Voltage | Rating: single-phase :AC 100V、400V Three-phase: AC 3×57.7V/100V(100V)、3×220V/380V(400V)、3×380V/660V(660V)(96 size only) Note:72 profile not suitable for high voltage applications | ||||
Overload:1.2 fold rating {continuous) : 2 fold rating for 1 second | |||||
Power consumption:<0.5VA | |||||
Current | Rating: AC IA、5A | ||||
Overload:1.2 fold rating(continuous);10fold rating for 1 second | |||||
Power consumption:<0.5VA | |||||
Output | Electric energy | Output mode:open-collector photo-coupler pulse | |||
Pulse constant: 10000imp/kWh(settable),see wiring diagram for details; | |||||
Communication | RS485port, Modbus -RTU protocol,DLT645 protocol(versions 07 and 97), baud rate 1200 ~ 38400 | ||||
Function | Switching input | Dry contact input, built-in power supply; | |||
Switching output | Output mode: Relay normally open contact output | ||||
Contact capacity: AC 250V/3A、 DC 30V/3A | |||||
Analog output | 0-5V,0 - 20mA,4 - 20mA | ||||
Accuracy class | Frequency:0.05Hz,Current、Voltage:0.2 class,Reactive power:l .0class,Reactive Electric energy:l .0class, active power:0.5class,active electric energy: 0.5class,2-31th harmonic measurement:±1% | ||||
Power supply | AC/DC 85-265V | power consumption≤10VA | |||
Security | Power frequency withstand voltage | Between Power supply//Switching Output// Current Input//voltage Input and Transmitting// Communication //Pulse Output//switching input AC 2 kV 1min; Between Power supply、switching output、Current Input、voltage Input AC 2 kV 1min; Between Transmitting、Communication、Pulse Output、switching input AC 1kV 1 min; | |||
Insulation resistance | Input、Output end to machine enclosure >100MΩ | ||||
Environment | Temperature | work: -25°C~+65°C storage: -40°C ~+80°C | |||
Humidity | ≤93%RH Non-condensing | ||||
Altitude | ≤2500m |
Note: The instrument Modbus RTU is compatible with dlt645 and only needs to set the corresponding address. See Chapter 6.3 for details.
Dimension Drawing(Unit:mm)
Outline | faceplate size | housing size | cutout size | ||||
width | height | width | height | depth | width | height | |
72 square | 75 | 75 | 66.5 | 66.5 | 94.3 | 67 | 67 |
96 square | 96 | 96 | 90 | 90 | 77.8 | 92 | 92 |
Figure 1 AMC72 appearance size
Figure 2 AMC96 appearance size
Figure 3 AMC72 installation dimensions
Figure 4 AMC96 installation dimensions
Installation method
1)Opening in fixed distribution cabinet
2)Take out the instrument and take out the clip
3) The instrument is mounted from the Front to the mounting hole, as shown in figure 5
4) Insert the instrument clasp to secure the instrument, as shown in figure 6
Certificate
Customers
Company Profile
Acrel Co.,Ltd.[Stock Code:300286.SZ] is a professional company in china who provides various systematic solutions of power monitoring,energy management and electrical safety for smart grid users.
Since June 2003,we have always been focused on the research,production and sales of intelligent electric meters.We concentrate on providing products and services to help customers improve electricity efficiency and safety.So far we have had the following comprehensive solutions for different applications:35(10)/0.4KV substation antomation system,power quality management system for medical location,precise distribution management system,smart lighting control system,remote orepayment metering system and motor control center.
Jiangsu Acrel Electrical Manufacturing Co.,LTD,our production base in Jiangyin City,Wuxi,provides guarantee for the industrialization and large-scare implementation of products.The annual production capacity of various meters is 2 million units,and more than 1.3 million units are sold in 2018.
Since the listing in 2012,our company has maintained steady growth.The company will adhere to the concept of“innovation,efficiency,unity,integrity”,adhere to steady operation and continuous innovation,and provide more high-quality products,services and silutions for power system users and micro-grid.
Contact