ASTM Standard Overhead Sizes Cable abc
USD $0.1 - $5 /Meter
Min.Order:3000 Meters
People\'s Cable Group Co., Ltd.
ASTM standard Overhead aluminum conductor xlpe insulated abc cable
1.Introduction
XLPE insulated ABC Cable are overhead power lines using several insulated phase conductors bundled tightly together, usually with a bare neutral conductor. They can improves safety and reliance of electrified wire netting.
2.Construction
Phase conductors are concentrically stranded EC Grade aluminum wires, insulated with either black weather resistant cross linked polyethylene (XLPE) or polyethylene (PE). The conductor insulation is marked with longitudinal ridges for phase identification..
Neutral messengers are concentrically stranded AAC or 6201 Alloy or ACSR. Neutral messenger can either be bare or insulated, depending on ABC design.
3.Standards
1). B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
2). B-231 Aluminum Conductors, Concentric-Lay-Stranded.
3). B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
4). B-399 Concentric-Lay Stranded 6201-T81 Aluminum Alloy Conductors.
5). B498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
6). Duplex Aerial Bundled Cable meets or exceeds all applicable requirements of ANSI/ICEA S-76-474
4.Type
Duplex xlpe insulated ABC Cable
Code*Word | Phase conductor | Bare Neutral Message | Nominal lay Length | Weight Per 1000 ft.(lbs.) | Allo wable Amp acitles | ||||||
Size (A WG) | Stranding | Insul Thick(Mils) | Size (AWG) | Stranding | Rated Strength (lbs.) | inches | XLP | POLY | XLP | POLY | |
AAC Neutral-messenger | |||||||||||
Pekingese | 6 | 1 | 45 | 6 | 7 | 563 | 10.36 | 61 | 61 | 85 | 70 |
Collie | 6 | 7 | 45 | 6 | 7 | 563 | 10.36 | 64 | 64 | 85 | 70 |
Dachshund | 4 | 1 | 45 | 4 | 7 | 881 | 10.36 | 92 | 92 | 115 | 90 |
Spaniel | 4 | 7 | 45 | 4 | 7 | 881 | 10.36 | 96 | 96 | 115 | 90 |
Doberman | 2 | 7 | 45 | 2 | 7 | 1350 | 14.88 | 147 | 147 | 150 | 120 |
Malemute | 1/0 | 9 | 60 | 1/0 | 7 | 1990 | 14.88 | 234 | 234 | 205 | 160 |
Triplex xlpe insulated ABC Cable
Code*Word | Phase conductor | Bare Neutral Message | Nominal lay Length | Weight Per 1000 ft.(lbs.) | Allo wable Amp acitles | ||||||
Size (A WG) | Stranding | Insul Thick(Mils) | Size (AWG) | Stranding | Rated Strength (lbs.) | inches | XLP | POLY | XLP | POLY | |
AAC Neutral-messenger | |||||||||||
Pateela | 6 | 7 | 45 | 6 | 7 | 563 | 14.88 | 103 | 103 | 85 | 70 |
Oyster | 4 | 7 | 45 | 4 | 7 | 881 | 14.88 | 154 | 154 | 115 | 90 |
Clam | 2 | 7 | 45 | 2 | 7 | 1350 | 20.58 | 233 | 233 | 150 | 120 |
Murex | 1/0 | 7 | 60 | 1/0 | 7 | 1990 | 20.58 | 374 | 374 | 205 | 160 |
Purpura | 1/0 | 9 | 60 | 1/0 | 7 | 1990 | 20.58 | 368 | 368 | 205 | 160 |
Nassa | 2/0 | 7 | 60 | 2/0 | 7 | 2510 | 25.42 | 462 | 462 | 235 | 185 |
Melita | 3/0 | 17 | 60 | 3/0 | 19 | 3310 | 29.97 | 562 | 562 | 275 | 215 |
Portunus | 4/0 | 18 | 60 | 4/0 | 19 | 4020 | 29.97 | 696 | 696 | 315 | 245 |
Nannynose | 336.4 | 19 | 60 | 336.4 | 19 | 6146 | 38.79 | 1118 | 1118 | 420 | 325 |
*Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Chihuahua/XLP) +Conductor temperature of 90 for XLP,75 for Poly;ambient temperature of 40;emissivity 0.2;2ft./sec.Wind in sun. |
Quadruplex xlpe insulated ABC Cable
Code*Word | Phase conductor | Bare Neutral Message | Nominal lay Length | Weight Per 1000 ft.(lbs.) | Allo wable Amp acitles | ||||||
Size (A WG) | Stranding | Insul Thick(Mils) | Size (AWG) | Stranding | Rated Strength (lbs.) | inches | XLP | POLY | XLP | POLY | |
AAC Neutral-messenger | |||||||||||
Clydessdale | 4 | 1 | 45 | 4 | 7 | 881 | 20.58 | 198 | 198 | 100 | 80 |
Pinto | 4 | 7 | 45 | 4 | 7 | 881 | 20.58 | 211 | 211 | 100 | 80 |
Mustang | 2 | 7 | 45 | 2 | 7 | 1350 | 25.42 | 318 | 318 | 135 | 105 |
Criollo | 1/0 | 9 | 60 | 1/0 | 7 | 1990 | 25.42 | 503 | 503 | 180 | 140 |
Percheron | 2/0 | 11 | 60 | 2/0 | 7 | 2510 | 29.97 | 619 | 619 | 205 | 160 |
Hanovarian | 3/0 | 17 | 60 | 3/0 | 19 | 3310 | 35.18 | 764 | 764 | 235 | 185 |
Oldenburg | 4/0 | 18 | 60 | 4/0 | 19 | 4020 | 35.18 | 945 | 945 | 275 | 210 |
Lippizaner | 336.4 | 19 | 80 | 336.4 | 19 | 6146 | 38.79 | 1519 | 1519 | 370 | 280 |
*Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Chihuahua/XLP) |
Main xlpe insulated abc cable
People's Cable Group Co., Ltd. was founded in 2007, located in Zhengzhou Gongyi economic development zone. We have 2 factories(Zhitian factory and Zhulin factory), occupies total area of more than 300,000 square meters, with building area 230,000 square meters. The real capital assets more than more than USD 10 million , with total 630 staff members, 65 of which are professional and technical experts. Zhitian factory is mainly specialized in PVC Insulated Wire, PVC and XLPE Insulated Power Cable with Voltage up to 35kV, Rubber Cable,Control cable and Welding Cables. And the Zhulin factory is mainly specialized in Aerial Bundled Cable(ABC Cable), Bare Overhead Power Transmission Line such as All Aluminum Conductor(AAC Conductor), All Aluminum Alloy Conductor(AAAC Conductor), Aluminum Conductor Steel Reinforced(ACSR Conductor), Aluminum Conductor Aluminum Clad Steel Reinforced (ACSR/AW), All Aluminum Alloy Steel Reinforced(AACSR), and Aluminum Conductor Aluminum Alloy Reinforced(ACAR). And Galvanized steel wire(GSW). Our products meet standards of GB, IEC, BS, DIN, ASTM, JIS, NF, AS/NZS, CSA, GOST and also supply according to customers’ unique requirements and specifications.
Packaged by wooden drum, wooden-steel drum, or steel drum.
FAQ:
(1).When can I get the price?
We usually quote within 6 hours after we get your inquiry. If you are very urgent to get the price, please
call us or tell us in your e-mail so that we will regard your inquiry priority.
(2).How can I get a sample to check your quality?
After price confirmation, you can require for samples to check our quality. Sample is free, but the freight
charge should be paid.
(3).How long can I expect to get the sample?
After you pay the freight charge and send us confirmed files, the samples will be ready for delivery in 3-7
days. The samples will be sent to you via express and arrive in 3-5 days. You can use your own express account orprepay us if you do not have an account.
(4).What about the lead time for mass production?
Honestly, it depends on the order quantity and the season you place the order.The best record we keep is
delivering 10 kilometers cable within a week. Generally speaking, we suggest that you start inquiry two months
before the date you would like to get the products at your country.