Technical parameters | Value |
input | Connection | 3-phase-3-wire, 3-phase-4-wire |
| frequency | 45-65HZ |
| voltage | rating: AC 100V、400V |
|
| overload: 1.2 fold rating {continuous) : 2 fold rating for 1 second |
|
| power consumption : <0.2VA |
| current | Rating: AC IA、5A |
|
| overload: 1.2 fold rating (continuous) ; 10fold rating for 1 second |
|
| power consumption : <0.2VA |
output | electric energy | Output mode: 2 channel open-collector photo coupler pulse |
|
| pulse constant: 10000 , 40000, 160000 imp/kWh |
| communication | RS485port, Modbus -RTU protocol |
| display | LED or LCD display, set multiplying power, alarm, switching indication at will;For 1 channel analog, display related programmable setting |
function | Switching input | 2channel or 4channel passive dry contact input mode |
| Switching output | Output mode: 2 channel relay NO contact output |
|
| contact capacity- 1A/30VDC 1A/250VAC |
| Analog output | Output mode: 1, 2 or 4 channel Output, 0 - 20mA,4 - 20mA programmable |
|
| load capacity≤500Ω |
accuracy class | Frequency 0.05Hz, reactive electric energy 1 class, others 0.5class |
power supply | DC100~350V;AV 85~265V; (In order to instrument wiring shall prevail ) | power consumption<5VA |
Security | Equipment withstand voltage= power supply, voltage input circuit 2kVAC; power supply,current circuit 2.5kV/1min(RMS) Insulation resistance- input, output end to housing >100MΩ |