Acrel Hot sale Demands and Multi-Tariff energy Multifunction Meter APM800/MD82 8DI+2DO
USD $290.5 - $290.5 /Piece
Min.Order:1 Piece
Jiangsu Acrel Electrical Manufacturing CO.,LTD
General
APM series meters have full power measurement, energy statistics, analysis of power quality and network communications and other functions, are mainly used for comprehensive monitoring of the quality of power supply network.
Parameters
Technical Parameters | Index | |||
Signal | Electrical network | Three-phase three-wire, three-phase four-wire, see the wiring diagram; | ||
Frequency | 45~65Hz; | |||
Voltage | Rated value:AC 100V、110V、400V、690V; | |||
Overload: 1.2 times rated value(continuous); 2 times rated value /1 second; | ||||
Power consumption:<0.5VA (per channel); | ||||
Current | Rated value: AC 1A, 5A, support 4 mm2 line access; | |||
Overload: 1.2 times rated value(continuous); 10 times rated value/1 second; | ||||
Power consumption:<0.5VA (per channel); | ||||
Measurement accuracy | Voltage、current and power | class 0.5s/class 0.2s (APM800、APM810/APM801) | ||
Active power | class 0.5s/class 0.2s (APM800、APM810/APM801) | |||
Reactive power | class 2 | |||
Harmonic | 1%(2rd~42nd)、2%(43rd~63rd) | |||
Switch inputs | Dry contact inputs, built-in power supply; | |||
Relay outputs | Contact type: open contact in main part, changeover contact in module; Contact capacity:AC 250V/3A DC 30V/3A; | |||
Pulse output of energy | Output mode: Optocoupler pulse with open collector; Pulse constant:4000(5A)、8000(1A) imp/kWh; | |||
Analog outputs | DC 0mA~20mA、4mA~20mA、0V~5V、1V~5V output, accuracy class 0.5%, load resistance ≤ 500Ω; | |||
Analog inputs | DC 0mA~20mA、4mA~20mA、0V~5V、1V~5V iutput, accuracy class 0.5% | |||
Storage card | Standard Capacity:4G,TF Card Up to 32G Capacity; | |||
Communication | RS485 interface/Modbus-RTU protocol and DLT645 protocol Profibus-DP interface/Profibus-DP protocol; RJ45 interface (Ethernet) / Modbus-TCP, http, DHCP and other protocols; | |||
Power supply | Working range: AC/DC 85V~265V or AC/DC 115~415V(P2); Power consumption: Power consumption of the main part ≤ 15VA; | |||
Safety | Power frequency withstand voltage | The power frequency withstand voltage between the shell and the auxiliary power supply, each input and output terminal group is AC 4kV/1min; The power frequency withstand voltage between the auxiliary power supply and each input and each output terminal group is AC 2kV/1min; The power frequency withstand voltage between the voltage input and other input/output terminal groups is AC 2kV/1min; The power frequency withstand voltage between the current input and other input/output terminal groups is AC 2kV/1min; The power frequency withstand voltage between the relay output and other input/output terminal groups is AC 2kV/1min; The power frequency withstand voltage between each terminal group of switch input, communication, analog output and pulse output is AC 1kV/1min; | ||
Insulation resistance | Inputs、outputs to the shell>100MΩ; | |||
Electromagnetic compatibility | Meet IEC 61000 standard (Level 4); | |||
Protection level | Display panel IP52 | |||
Environment | Operating temperature: -20 °C ~ +65 °C; Storage temperature: -20°C~+70°C; Relative humidity: ≤95% without condensation; Altitude: ≤2500m; | |||
Standards | IEC 60068-2-1 IEC 60068-2-2 IEC 60068-2-30 | Environmental Testing-Part 2-1:Tests Test A:Cold IDA Part 2-1:Tests Test B:Dry heat Part 2-30:Tests Test Db:Damp heat,cyclic(12+12h) | ||
IEC 61000-4 | Electromagnetic compatibility-Testing and measurement techniques | |||
IEC 61557-12 | Electrical safety in low voltage distribution system up to 1000V a.c. and1500V d.c –Equipment for testing,measuring or monitoring of protective measures- Part12: Performances measuring and monitoring devices(PMD) | |||
IEC 62053-22 | Electricity metering equipment (a.c.)-Particular requirements - Part22:Static meter for active energy(class 0.2s and 0.5s) |