3/3 Phase High Frequency Online UPS 40kVA/36kw with Parallel Function and 380VAC/400VAC/415VAC Input and Output
USD $1000 - $8000 /Piece
Min.Order:1 Piece
Shenzhen UPSEN Electric Co., Ltd.
3/3 Phase High Frequency Online UPS 40Kva/36Kw with Parallel Function and 380Vac/400Vac/415Vac Input and Output
1: 3 Phase 40Kva UPS with 380/400/415Vac or 190/208/220vac Input/output
2: 40Kva UPS Power with 0.9 Power Factor Output
3: 40Kva UPS with Pure sine wave output
4: High Frequency transformerless type UPS
5: UPS IGBT, PWM Inverter together and input PFC
UPS Perfect Applications
Internet Servor, Internet Data Center), Medium-scale network system / computing center, bank
And securities, business server group, Medium-scale office automation, precision equipment, etc.
UPS Features
Output PF0.9
3 Phase Input/Output for both 190/208/220Vac and 380/400/415Vac
Complete digital control technology
Excellent electrical properties
High input power factor 0.99, green and energy-saving
Dual AC input source supportable
Strong environmental adaptability
Comprehensive protection measures
Similar modular design
Intelligent battery management (ABM)
Model | ES3310 | ES3320 | ES3330 | ES3340 | ES3360 | ES3380 | ||
Capacity/Rating Power | 10KVA/ 9KW | 20KVA/ 18KW | 30KVA/ 27KW | 40KVA/ 36KW | 60KVA/ 54KW | 80KVA/ 72KW | ||
AC Input | Rated voltage | 190/208/220Vac Or 380/400/415Vac (Line-Line) | 380/400/415Vac (Line-Line) | |||||
Input connection | Three phase four wires | |||||||
Power factor | Above 0.99 | |||||||
THDI | Less 5% | |||||||
Voltage range | 150-270Vac or 280-480Vac(Line voltage) | |||||||
Frequency | 40-70Hz | |||||||
Bypass | 150-270Vac or 280-480Vac(Line-Line)+/- 15% | |||||||
Output | voltage precision | ±0.5% | ||||||
Dynamical | Less 5% ( 0 ~ 100% load step) | |||||||
voltage transient | ||||||||
THDU | THD less 3% (linear load), 5%(non-linear load) | |||||||
Power factor | 0.9 (lag) | |||||||
Frequency tracking range | 50/60Hz±3Hz | |||||||
Frequency precision | ±0.05%(Battery mode) , ±3hz(Line mode) | |||||||
OUTPUT | phase displacement | 120±0.5°(Balance or imbalance load ) | ||||||
Frequency tracking rate | Less 1Hz/s | |||||||
Overload capability | 105% long time operation | |||||||
125%,transfer to bypass after 10 minutes | ||||||||
Above 150%, transfer to bypass after 1s | ||||||||
Bypass | Above 180%, long time operation | |||||||
overload | Above 180%, last for 1s | |||||||
Transfer time | 0ms | |||||||
System | ||||||||
System efficiency | Above 92%;98%(ECO) mode | |||||||
Display | Touch screen LCD+LED | |||||||
EMC | IEC62040-2 | |||||||
IEC61000-4-2 (ESD) | ||||||||
IEC61000-4-3 (RS) | ||||||||
IEC6100-4-4 (EFT) | ||||||||
IEC6100-4-5 (Surge) | ||||||||
Noise (1m) | Less 60dB | |||||||
Insulating resistance | Above 2M (500VDC) | |||||||
Insulating intensity | (input, output to PE) 2820Vdc, leakage current lower than 3.5mA, no flashover in 1min | |||||||
Surge protection | Meet the requirement of IEC60664-1class,endure surge of 1.2/50us+8/20us higher than 6KV/3KA | |||||||
IP class | IP30 | |||||||
Battery configuration | ||||||||
Installation(DC) | 384/432/480Vdc adjustable | |||||||
Connection | Bottom cable connection in front | |||||||
Charger | 20% Power capacity(Adjustable) | |||||||
Dimension (W×D×H)mm | Long-run model | 500×717×798 | 720×900×1450 | |||||
Inbuilt batt. | 500×717×1150 | 500×717×1550 | ||||||
Weight (Kg) | Long-run model | 40 | 65 | 95 | 100 | 240 | 260 | |
Inbuilt batt. | 125 | 175 | 255 | 295 | ||||
32/36/40pcs*7AH/9AH or 72pcs*7AH/9AH |