Eemerson 2-Way Solenoid Valves types 200RB6T5T,240RA16T9T,240RA20T13M introduction
Directly actuated: The magnetic field of the
solenoid coil forces a movement of the plunger and
thus causes the opening of the valve seat.
Servo actuated: The magnetic field of the solenoid
coil is only utilized for the opening of the pilot valve
seat. The necessary energy to actuate the piston
or diaphragm of the main valve seat is provided by
the refrigerant flow and results in a certain pressure
drop.
Minimum pressure drop
Directly actuated solenoid valves do not require a
minimum pressure drop for proper operation.
Servo operated solenoid valves require a minimum
pressure drop of approximately 0.05 bar to remain
fully open. In case of insufficent refrigerant flow this
value will not be reached and the solenoid valve
may close unintentionally. These closures may lead
to malfunctions and oscillations in the refrigeration
circuit. Improper sizing of solenoid valves (i.e. use of
excessively large solenoid valves) is the main cause of
this effect. This is particularly important in capacity
controlled refrigeration circuits.
Therefore the decisive factor for proper solenoid
valve sizing is the respective capacity of the valve
and not its connection size.
Formula for calculating the actual pressure drop of
a solenoid valve:
∆ p1 = ∆ p2 x (Q n1 /Q n2 ) 2
∆ p1 : Actual pressure drop
∆ p2 : Nominal pressure drop at Q n1
Q n1 : Calculated nominal capacity
Q n2 : Nominal capacity of selected valve
Maximum Operating Pressure Differential
(MOPD)
MOPD is the maximum pressure differential between
inlet and outlet of the solenoid valve which permits
proper opening of the valve. When used with ALCO
AC solenoid coils all ALCO solenoid valves employ
25 bar MOPD.
Operation in conjunction with DC solenoid coils lead
to reduced MOPD values depending on valve type
and size.
The DS2 Chopper Plugs allow the use of
24VAC coils with 24VDC by converting the DC in
an AC voltage. Please contact ALCO application
engineering for additional details.
Eemerson 2-Way Solenoid Valves types 200RB6T5T,240RA16T9T,240RA20T13M Features
Compact size
• Snap-on clip for attaching solenoid coils
• No disassembly necessary for soldering
Standards
• 240 RA 16T11 and 20 are CE marked per PED
Type Nominal Capcity Q n (kW)
Liquid Hot Gas Suction Gas
R 404A R 404A kv-value ∆p min
R 134a R 22 R 507 R 407C R 134a R 22 R 507 R 407C R 134a R 22 R 507 R 407C m 3 /h bar
110 RB 2 3,5 3,8 2,5 3,6 1,6 2,0 1,7 2,1 0,2 0
200 RB 3 6,6 7,1 4,6 6,8 3,0 3,7 3,2 3,9 0,4 0,05
200 RB 4 15,5 16,8 10,9 16,1 7,1 8,8 7,5 9,2 0,9 0,05
200 RB 6 27,3 29,5 18,9 28,0 12,5 15,4 13,1 16,1 1,6 0,05
240 RA 8 36,3 39,3 25,2 37,3 16,7 20,5 17,4 21,4 4,2 5,6 4,6 5,2 2,3 0,05
240 RA 9 76,2 82,5 52,9 78,4 35,1 43,1 36,5 44,9 8,8 11,7 9,7 10,9 4,8 0,05
240 RA 12 85,7 92,8 59,5 88,1 39,4 48,4 41,1 50,5 9,9 13,1 10,9 12,3 5,4 0,05
240 RA 16 139,1 150,5 96,5 142,9 64,0 78,5 66,6 81,9 16,0 21,3 17,7 19,9 8,8 0,05
240 RA 20 202,6 219,3 140,7 208,3 93,2 114,4 97,1 119,3 33,0 31,0 25,7 29,0 12,8 0,05