560kW SDEC Diesel Engine Generator with 1250A Change-Over Switch for Building Back-up Power Supply
USD $15000 - $35000 /Set
Min.Order:1 Set
560kW SDEC Diesel Engine Generator with 1250A Change-Over Switch for Building Back-up Power Supply
700kVA SDEC Diesel Generator Supply Scope:
Diesel Generator Set | |||||||
Model | ST-SH700 | ||||||
Standby Output (50Hz) | 700kVA / 560kW | ||||||
Prime Ouptut (50Hz) | 636kVA / 509kW | ||||||
STANDARD FEATURES | |||||||
Supply Scope | |||||||
1. Engine with SDEC Shangchai brand model SC27G900D2 | |||||||
2. Alternator with Sutong Power brand model S354G520 | |||||||
3. Automatic Start / Stop control panel | |||||||
4. Dry type air fillter, fuel filter, oil filter | |||||||
5. 24V D.C automatic battery charger. | |||||||
6. Max. 50 degree celsius radiator | |||||||
7. Batteries, rack and cable | |||||||
8. Ripple flex exhaust pipe, flange and muffler | |||||||
9. Circuit breaker | |||||||
10. 1250A ATS | |||||||
11. Complete users' manual | |||||||
DIESEL GENERATOR RATINGS | |||||||
Voltage (V) | Frequency (Hz) | Phase | Standby Amps. (A) | Standby Output | Prime Output | ||
kVA | kW | kVA | kW | ||||
240/415 | 50 | 3 | 973.9 | 700 | 560 | 636 | 509 |
230/400 | 50 | 3 | 1010.4 | 700 | 560 | 636 | 509 |
220/380 | 50 | 3 | 1063.6 | 700 | 560 | 636 | 509 |
Prime Output: Prime output is available for an unlimited number of annual hours in variable load application, in accordance with GB/T2820-97 (eqv ISO8528); a 10% overload capability is avaiable for a period of 1 hour with a 6-hours period of operation. | |||||||
Standby Output: The standby output is applicable for supplying emergency power for duration of a utility power interruption. No overlad, utility parallel or negotiated outage operation capability is available at this rating. | |||||||
SALE PROMISES | |||||||
1. Sutong Power provides a full line of brand new and high quality products. Every unit is strictly factory tested. | |||||||
2. Warranty is according to our standard conditions: 12 months or 1,000 running hours, subject to which comes first. | |||||||
3. Service and parts are avaiable from Sutong Power or distributors in your location. |
ENGINE SPECIFICATION
Manufacturer | Shanghai Diesel Engine Co., Ltd | ||||||
Engine Model | SC27G900D2 | ||||||
Engine Type | 12-Cylinder Diesel | ||||||
Aspiration | Turbocharged and Air-Air InterCooled | ||||||
Cooling Method | Water Cooling | ||||||
Governor | Electric | ||||||
Compression Ratio | 14.9:1 | ||||||
Engine Max Output at rate 1500R.P.M. | kWm | 662 | |||||
BHP | 887 | ||||||
Displacement | Liters | 26.6 | |||||
Engine Speed | R.P.M. | 1500 | |||||
Bore x Stroke | mm | 135 x 155 | |||||
Fuel Comsunption at 100% load | Liters / H | 135 | |||||
Coolant Capacity | Liters | 68 | |||||
Intake Air Flow at rate output | Liter / S | 950 | |||||
Exhaust Gas Temp. at rate output | °C | 650 | |||||
Exhaust Gas Flow at rate output | Liter / S | 2550 |
ALTERNATOR SPECIFICATION
Manufacturer | Fujian Sutong Power Limited | ||||||
Model | S354G520 | ||||||
Max Output | kVA | 715 | |||||
Rate Speed | R.P.M. | 1500 | |||||
Rate Frequency | Hz | 50 | |||||
Altitude | M | ≤1000 | |||||
Alternator Type | Single bearing, brushless type | ||||||
Connection Type | Three phase, four wire | ||||||
Protection Grade | IP23 | ||||||
Insulation Class | H | ||||||
Voltage Regulation | AVR | ||||||
Standards | Compliance with GB755, BS5000, NEMA MG1-22, IEC-34, CSA C22-100 and AS1259 Standards. | ||||||
Smartgen Controller Specification:
Control supervision and protection panel is mounted on | ||||||
the genset base frame. | ||||||
The control panel is equipped as follows: | ||||||
Automatic Control Panel | ||||||
Control panel: | ||||||
-- Control with AMF module | ||||||
-- Static with auto. battery charger | ||||||
-- Emergency stop push button | ||||||
-- ATS Connection | ||||||
a) Generator set controller model HGM 6120 features: | c) Alarms: | |||||
-- The module is used to monitor the generator set | -- Over and Under Speed | |||||
start & stop. | -- Low and High Battery Voltage. | |||||
-- Micro-processor based design | -- Start and Stop Failure | |||||
-- Monitors engine performance and AC power output | -- Charge Fail | |||||
-- LED alarm indication and Sound alarm. | -- Over Current | |||||
-- Under / Over Generator Voltage | ||||||
b) Metering via LED display: | -- Low Oil Pressure | |||||
-- Mains voltage: Uab, Ubc, Uca | -- Emergency Stop | |||||
-- Generator voltage: Uab, Ubc, Uca | -- High Engine Temperature | |||||
-- Generator current: Ua, Ub, Uc | -- Over Load | |||||
-- Generator temp.: ℃/℉ both display | ||||||
-- Generator frequency: Hz | d) LED Indications | |||||
-- Generator active power: kW | Four configurable LED's like: | |||||
-- Generator starts count: 999999 times (Max) | -- Generator available | |||||
-- Generator pressure: kPa/Psi/Bar both display | -- Generator on load |
Options:
-- Daily Fuel Tank | -- Parallel Panel | -- Remote Control Panel | -- Soundproof Type | |||
-- Engine Heater | -- Permanent Magnet | -- Auto. Transfer Switch | -- Trailer Type | |||
-- Water Heater | Generator (PMG) | -- Switch Box | -- Spare Parts |