Danfoss EKC312-084B7250 electronic superheat controller introduction
The controller and valve can be used wherethere are requirements to accurate control of superheat in connection with refrigeration.
• Processing plant (water chillers)
• Cold store (air coolers)
• A/C plant
Danfoss EKC312-084B7250 electronic superheat controller Features
The evaporator is charged optimally – even when there are great variations of load and suction pressure.Energy savings – the adaptive regulation of the refrigerant injection ensures optimum utilisation of the evaporator and hence a high suction pressure.The superheating is regulated to the lowest possible value.
Danfoss EKC312-084B7250 electronic superheat controller Operation
Superheat function
y Adaptive superheat
MOP
The MOP function limits the valve’s opening degree as long as the
evaporating pressure is higher than the set MOP value.
External start/stop of regulation
The controller can be started and stopped externally via a contact
function connected to input terminals 1 and 2. Regulation is
stopped when the connection is interrupted. The function must be
used when the compressor is stopped. The controller then closes
the solenoid valve so that the evaporator is not charged with
refrigerant.
Alarm relay
The relay for the alarm function works in such a way that the
contact is cut in in alarm situations and when the controller is
de-energised.
PC operation
The controller can be provided with data communication so that it
can be connected to other products in the range of ADAP-KOOL®
refrigeration controls. In this way operation, monitoring and data
collection can be performed from one PC – either on the spot or in
a service company.