TUV 3 core 25 35KV armoured LSOH power cable
USD $9.00 - $15.00 /Meter
Min.Order:3000 Meters
Shuanglin Communication Technology Co., Ltd.
QYEEY10 5KV EPR/EPDM Insulated EPR sheathed Galvanized steel tape Interlock armoured ESP cable
QYYEQEY 5KV EPR/EPDM Insulated lead sheathed Interlock Galvanized steel tape armoured ESP cable
Factory Hebei China 5kv polyimide f46 insulation submersible oil pump cable
Factory Hebei China Water/Oil resistance Submersible Pump Cable
Medium voltage 3 core cu/xlpe/LSOH/swa/LSOH armoured power cable
1 Construction
one core
conductor: copper or aluminium
insulation: xlpe
inner sheath: LSOH- low smoke halogen free
armour: aluminum wire or steel tap
sheath:LSOH- low smoke halogen free
standard:IEC60502.2 .IEC60332. (fire test).IEC60754(halogen free test). IEC61034(smoke density)
three core
conductor: copper or aluminium
insulation: xlpe
inner sheath: LSOH- low smoke halogen free
armour: steel wire galvanized or steel tap
sheath: LSOH- low smoke halogen free
standard:IEC60502.2.IEC60332..IEC60754. IEC61034
2 Application:
It is used to transmit and distribute power in power transmission and distribution system of 35kV or lower. It is generally applied to the fields including power, construction, mines, metallurgy, petrochemical industry and communication in complete replace of oil immersed paper insulated power cable and in partial replace of PVC insulated power cable. Power cables for power networks, underground, outdoors and in cable ducting
3 Using features:
1.Rated voltage: Uo/U:3.6/6kV, 6/10kV(11kV), 12/20kV(24kV), 19/33kV, 26/35kV(35kV).
2. No. of core: Single core or three cores.
3. The highest allowed operating temperature of conductor for long-term working is 90oC. In short-circuit (Max. long-term is no more than 5 seconds). The highest temperature for conductor is no more than 250℃.
4. D.C. resistance of the conductor complies with the stipulations of 3.6/6kV, 6/10kV(11kV), 12/20kV(24kV), 19/33kV, 26/35kV(35kV).
5. The environment temperature should be no lower than 0oC when lay. Otherwise it should be preheated.
6. The cable is laid without horizontal drop limit.
7. Working Frequency Voltage Test: 3.5Uo/5min without puncture.
8. Partial Discharge Test: The discharge volume should be no more than 10pC under 1.73Uo for the cable.
9. Minimum Bending Radius
Single core - Fixed: 15 x overall diameter
3 core - Fixed: 12 x overall diameter
(Single core 12 x overall diameter and 3 core 10 x overall diameter where bands are positioned adjacent to joint or terminations provided that the bending is carefully controlled by the use of a former)
Note:
The single core armored cables are used for D.C. system only. If used for A.C. system, the magnetic isolation should be applied on the steel armor wires of non-magnetical materials should be used.
HeBei huatong wires&cables Group Co.,ltd.
which founded in1993,covers 15,000 square meters.With 400 sets of manufacturing machines and 200 pieces of equipment available for testing and inspecting,the company's annual mannufacturi-ng capacity has reached 450 minllionUS dollars.
The enterprise has adapted international a-dvanced mannagement standards by fully implementing the accreditation of ISO9001Quality con-trol system, ISO1004 Envrionment management system,and OHSAS18001 Occupational health and safety management system.
Huatong's products which consist of 15 series of cables and tens of thousands of specifications are widely used in different key national projects and industries .Our products are well liked by domestic and international customers that they have been exported to various countries and areas including the US,Netherlands, Italy,Russia,UK,Australia,Ethiopia,Ghaha,congo,Middle East ,and Southeast Asia.
(1).When can I get the price?
We usually quote within 6 hours after we get your inquiry. If you are very urgent to get the price, please call us or tell us in your e-mail so that we will regard your inquiry priority.
(2).How can I get a sample to check your quality?
After price confirmation, you can require for samples to check our quality. Sample is free, but the freight charge should be paid.
(3).How long can I expect to get the sample?
After you pay the freight charge and send us confirmed files, the samples will be ready for delivery in 3-7 days. The samples will be sent to you via express and arrive in 3~5 days. You can use your own express account orprepay us if you do not have an account.
(4).What about the lead time for mass production?
Honestly, it depends on the order quantity and the season you place the order.The best record we keep is delivering 10 kilometers cable within a week.
Dedication makes profession