High Frequency Modern Design Radar Liquid Sensors Level Transmitters
USD $420 - $650 /Piece
Min.Order:1 Piece
Xi'an Shelok Instrument Technology Co., Ltd.
High Frequency Modern Design Radar Liquid Sensors Level Transmitters
Description High Frequency Modern Design Radar Liquid Sensors Level Transmitters
Radar level sensor emits a very narrow microwave pulse, the pulse to the speed of light in the space, encountered the surface of the measured medium, part of its energy is reflected back, the same antenna to receive. The time interval between the transmitting pulse and the receiving pulse is proportional to the distance from the antenna to the surface of the measured medium to calculate the distance from the antenna to the surface of the measured medium.
Detailed Images High Frequency Modern Design Radar Liquid Sensors Level Transmitters
Specification High Frequency Modern Design Radar Liquid Sensors Level Transmitters
High Frequency Modern Design Radar Liquid Sensors Level Transmitters | |||
Model | SLK-NYRD801 | SLK-NYRD802 | SLK-NYRD803 |
Measuring | 0 ~ 20 Meters, 0 ~ 35 Meters | ||
Working | 6.8Ghz | ||
Power Supply | 24V DC (±10%) | ||
Current Signal | 4 ~ 20mA, RS485 (Optional) | ||
Accuracy | <0.1% | ||
Resolution | 1mm | ||
Environment | -40℃ ~ 250℃ | ||
Pressure Range | 1 ~ 40bar | ||
Interface | 2Pcs M20×1.5 or 2Pcs 1/2Npt (Cable OD 5 ~ 9mm) | ||
Application | Power Plants, Oil Fields, Chemicals, Metallurgy, Cement, Water Treatment, Paper Making and others | ||
Beam Angle | 24" | 24" | 14" 16" 20" |
Antenna | PP or PTFE | PTFE | SS |
Process Connection | Thread (G11/2A or 11/2NPT) | Flange | Flange |
Principle High Frequency Modern Design Radar Liquid Sensors Level Transmitters
Radar level transmitter antenna microwave pulse is narrow, the downward transmission antenna. Microwave exposure to the medium surface is reflected back again by the antenna system receives, sends the signal to the electronic circuit automatically converted into level signals (because the microwave propagation speed, electromagnetic wave to reach the target and the reflected back to the receiver this time is almost instantaneous).
Datum measurement: Screw thread bottom or the sealing surface of the flange.
Note: Make sure the radar level meter the highest level cannot enter the measuring blind
area (Figure D shown below).
Features High Frequency Modern Design Radar Liquid Sensors Level Transmitters
Ø Small antenna size, easy to install; Non-contact radar, no wear, no pollution.
Ø Almost no corrosion, bubble effect; almost not affected by water vapor in the atmosphere, the temperature and pressure changes.
Ø Serious dust environment on the high level meter work has little effect.
Ø A shorter wavelength, the reflection of solid surface inclination is better.
Ø Beam angle is small, the energy is concentrated, can enhance the ability of echo and to avoid interference.
Ø The measuring range is smaller, for a measurement will yield good results.
Ø High signal-to-noise ratio, the level fluctuation state can obtain better performance.
Ø High frequency, measurement of solid and low dielectric constant of the best choice.
The Installation Requirements
Installation guide:Be installed in the diameter of the 1/4 or 1/6. Note: the distance between the tank wall minimum distance should be tank high 1/10.
Note: 1. datum
2.The container center or axis of symmetry
The top conical tank level, can be installed at
the top of the tank is intermediate, can guarantee the measurement to the conical bottom.
Typical installation errors:
Ø Conical tank cannot be installed above the feed port.
Note: outdoor installation should adopt sunshade.
1. Correct
2. Error rainproof measures
Ø The instrument cannot be installed in the arched or domed roof intermediate. In addition to produce indirect echo is also affected by the echoes. Multiple echo can be larger than the real value of signal echo, because through the top can concentrate multiple echo. So cannot be installed in a central location.
1. Correct
2. Error
Ø There are obstacles affecting measurement needed reflection plate.
1. Correct
2. Error
Related products
FAQ
Q:How long will you reply me?
A:We will contact you as soon as possible but within 12 hours
Q: Can I get some samples?
A: Yes, Sample order is available for quality check and market test. But you have to pay the express cost.
Q: How soon can you arrange your production?
A: Once getting your product confirmation and receiving the prepayment, the production will be started immediately.
Q: What's delivery time?
A: It usually takes about 3-5 working days for small order and 10-15 days for big order.
Q:How do you control your quality ?
A: Three inspection steps(of original, production, and finished goods) + good warranty service(1 year free to change a new one without any human damage factors).
Q: What certificates do you have ?
A:ISO9000, CE, Explosion-proof certification, RoHs ready. And before the delievry of goods, quality and safety inspection certification issued by third parts also can be offered.
Q:Could I visit your factory?
A:Very welcome! Fly to Xian Yang air port. It was a big pleasure for us.
Q: What's your warranty terms?
A: We offer 12 months warranty time.
Q:can you provide OEM & Customized service?
A:Yes, OEM and ODM are both available, we have the professional R&D dept which can provide professional solutions for you.
Company Information
Shelok Introduction
Shelok considers itself not only a manufacture but more conprehensively a provider of industry specific customer-oriented solutions.Our profound understanding of product application and strong technical backgrounds ensure you the best product solution and achieve a greater success.
Xi'an Shelok Instrument Technology co.,ltd is a professional R&D center and manufacture of measuring instruments.And here's a variety of products for you choice: pressure transmitters,temperature transmitters,flow transmitters,weighing instruments and so on.Our products have been made by advanced technology, with high quality, fast delivery period, which have attracted so many domestic and foreign customers.