Fire fighting pump
USD $999 - $35999 /Set
Min.Order:1 Set
SINCO FIRE AND SECURITY CO., LIMITED
Introduction
XBC series Diesel engine fire-fighting pump is a new-style fire fighting equipment, which is developed upon the fitted fire fighting pumps (single stage single suction type, single-stage dual-suction type and sectional multistage type), can be divided into several series. The equipment has a wide range of pressure and temperature and can be used for almost every occasion necessary for fire fighting purpose.The diesel engine fitted with the equipment is an excellent product domestic or imported, features good starting performance, strong overload capacity, compact structure, easy maintenance and use and high degree of automation.
XBD Series Electricity Fuel Centrifugal Fire Fighting Water Pump is the new middle and low pressure fire fighting product, which researched by our company according to the latest standard(GB 6425-1998) of fire fighting pump in our country, its motor and fire pump is connected directly, which simplified the middle transmitting structure, and strengthen operation's stability. Its building area is less 30% than common horizontal fire pump, the shaft seal adopts hard alloy mechanical seal without leakage, its inlet and outlet can be installed at any position and any direction like valve, its noise is low, maintenance is convenient, shake is little and so on. XBD series include four structural types to meet the different requirements of users, including vertical single-stage fire pump, vertical multistage fire pump, horizontal single-stage fire pump and horizontal multistage fire pump.
Specification
Name | Electric or diesel engine driven centrifugal fire fighting water pump |
Pumped medium | Water or other liquid |
Fire pump flow | 1.5~1550m3/h |
Fire pump head | 16~380m |
Inlet & Outlet diameter | DN25~600mm |
Fire Pump material | Cast iron/Stainless steel |
Speed | 980~3500rpm |
Diesel / motor power | 0.75~580kW |
Diesel cylinder numbers | 1/2/4/6/8 |
Straing method | 12/24V battery starter for diesel engine |
Motor Electric | 110~525V |
Medium temperature | -15~+120℃ |
Components:
1.Electric pump: | kinds of end suction pump, split case pump, multistage pump. | |
2.Diesel pump: | Flow is the same with electric pump. | |
3.Jockey pump: | horizontal or vertical, small flow, | |
4.Control panel: | control the pumps automatically with overload, overcurrent protection | |
5.Accessories: | check valve, gate valve, pressure tank (0.6mpa, 1.0mpa, 1.6mpa) | |
XBC Model Form | |||||||||
Model | Speed | Capacity | Pressure | Effi | NPSH | Shaft Power | Diesel Power | Inlet/Outlet | Weight |
3/10 | 2000 | 10 | 0.3 | 71 | 2.5 | 5.5 | 7.5 | 100/65 | 91 |
3/20 | 2000 | 20 | 0.3 | 71 | 3 | 9.5 | 13.8 | 100/65 | 91 |
3/30 | 2000 | 30 | 0.3 | 69 | 3.8 | 16.8 | 20.6 | 125/100 | 129 |
3/40 | 2000 | 40 | 0.3 | 77 | 4.8 | 18.5 | 23.2 | 125/100 | 129 |
4/10 | 2000 | 10 | 0.4 | 71 | 2.5 | 7.4 | 13.8 | 100/65 | 91 |
4/20 | 2000 | 20 | 0.4 | 77 | 3 | 11.2 | 15.3 | 125/100 | 129 |
4/30 | 2000 | 30 | 0.4 | 74 | 3.6 | 18.2 | 26.5 | 125/100 | 145 |
5/10 | 2000 | 10 | 0.5 | 65 | 4.2 | 8.7 | 13.8 | 100/65 | 120 |
5/20 | 2000 | 20 | 0.5 | 65 | 4.5 | 19.9 | 26.5 | 100/65 | 120 |
5/30 | 2000 | 30 | 0.5 | 74 | 4.5 | 25.7 | 35.3 | 125/100 | 145 |
5/40 | 2000 | 40 | 0.5 | 74 | 4.9 | 32.8 | 35.5 | 125/100 | 145 |
5/50 | 1500 | 50 | 0.5 | 75 | 2.8 | 36.3 | 58 | 150/125 | 212 |
5/100 | 1500 | 100 | 0.5 | 81 | 3.8 | 67.2 | 105 | 200/150 | 245 |
5/110 | 1500 | 110 | 0.5 | 81 | 4.5 | 68.4 | 105 | 200/150 | 245 |
6/10 | 2000 | 10 | 0.6 | 65 | 2.5 | 11.5 | 15.3 | 100/65 | 120 |
6/20 | 2000 | 20 | 0.6 | 74 | 3 | 19.7 | 26.5 | 125/100 | 145 |
6/30 | 2000 | 30 | 0.6 | 74 | 3.6 | 29.7 | 40.4 | 125/100 | 145 |
4/30 | 1500 | 30 | 0.4 | 75.5 | 4.1 | 15.6 | 20.6 | 125 | 475 |
6/30 | 1500 | 30 | 0.6 | 75.5 | 4.1 | 23.4 | 31.6 | 125 | 555 |
8/30 | 1500 | 30 | 0.8 | 75.5 | 4.1 | 31.2 | 34.3 | 125 | 640 |
10/30 | 1500 | 30 | 1 | 75.5 | 4.1 | 39 | 58 | 125 | 726 |
12/30 | 1500 | 30 | 1.2 | 75.5 | 4.1 | 46.8 | 75 | 125 | 840 |
14/30 | 1500 | 30 | 1.4 | 75.5 | 4.1 | 54.6 | 75 | 125 | 923 |
16/30 | 1500 | 30 | 1.6 | 75.5 | 4.1 | 62.4 | 75 | 125 | 1008 |
18/30 | 1500 | 30 | 1.8 | 75.5 | 4.1 | 70.2 | 110 | 125 | 1093 |
6/40 | 1500 | 40 | 0.6 | 77 | 3.9 | 32.8 | 58 | 150 | 490 |
9/40 | 1500 | 40 | 0.9 | 77 | 3.9 | 49.3 | 75 | 150 | 575 |
12/40 | 1500 | 40 | 1.2 | 77 | 3.9 | 65.7 | 75 | 150 | 660 |
15/14 | 1500 | 40 | 1.5 | 77 | 3.9 | 82.1 | 110 | 150 | 745 |
18/40 | 1500 | 40 | 1.8 | 77 | 3.9 | 98.5 | 160 | 150 | 830 |
8/80 | 1500 | 80 | 0.8 | 77 | 4.7 | 85.2 | 110 | 200 | 667 |
12/80 | 1500 | 80 | 1.2 | 77 | 4.7 | 127.7 | 160 | 200 | 787 |
16/80 | 1500 | 80 | 1.6 | 77 | 4.7 | 170.3 | 220 | 200 | 907 |
20/80 | 1500 | 80 | 2 | 77 | 4.7 | 212.3 | 279 | 200 | 1027 |
25/80 | 1500 | 80 | 2.5 | 77 | 4.7 | 255.5 | 279 | 200 | 1147 |
18/125 | 1500 | 125 | 1.8 | 79 | 4.9 | 229.2 | 338 | 250 | 1750 |
XBD Model Form | ||||||
model | capacity | pressure | speed | effeciency | power | npsh |
(L/s) | (MPa) | (r/min) | (%) | (Kw) | (NPSH)r(m) | |
XBD1.8/5-50W | 5 | 0.18 | 1450 | 65 | 2.2 | 3.2 |
XBD2.7/5-50W | 5 | 0.27 | 1450 | 65 | 3 | 3.2 |
XBD3.6/5-50W | 5 | 0.36 | 1450 | 65 | 4 | 3.2 |
XBD4.5/5-50W | 5 | 0.45 | 1450 | 65 | 5.5 | 3.2 |
XBD5.4/5-50W | 5 | 0.54 | 1450 | 65 | 5.5 | 3.2 |
XBD6.3/5-50W | 5 | 0.63 | 1450 | 65 | 7.5 | 3.2 |
XBD7.2/5-50W | 5 | 0.72 | 1450 | 65 | 7.5 | 3.2 |
XBD8.1/5-50W | 5 | 0.81 | 1450 | 65 | 7.5 | 3.2 |
XBD2.3/10-75W | 10 | 23 | 1450 | 68 | 5.5 | 3 |
XBD3.4/10-75W | 10 | 0.34 | 1450 | 68 | 7.5 | 3 |
XBD4.6/10-75W | 10 | 0.46 | 1450 | 68 | 11 | 3 |
XBD5.5/10-75W | 10 | 0.55 | 1450 | 68 | 11 | 3 |
XBD6.9/10-75W | 10 | 0.69 | 1450 | 68 | 15 | 3 |
XBD8.0/10-75W | 10 | 0.8 | 1450 | 68 | 15 | 3 |
XBD9.2/10-75W | 10 | 0.92 | 1450 | 68 | 18.5 | 3 |
XBD10.3/10-75W | 10 | 1.03 | 1450 | 68 | 18.5 | 3 |
XBD2.9/20-100W | 20 | 0.29 | 1450 | 72 | 11 | 3.5 |
XBD4.3/20-100W | 20 | 0.43 | 1450 | 72 | 15 | 3.5 |
XBD5.8/20-100W | 20 | 0.58 | 1450 | 72 | 22 | 3.5 |
XBD7.2/20-100W | 20 | 0.72 | 1450 | 72 | 30 | 3.5 |
XBD8.6/20-100W | 20 | 0.86 | 1450 | 72 | 30 | 3.5 |
XBD10.1/20-100W | 20 | 1.01 | 1450 | 72 | 37 | 3.5 |
XBD11.5/20-100W | 20 | 1.15 | 1450 | 72 | 45 | 3.5 |
XBD13.0/20-100W | 20 | 1.3 | 1450 | 72 | 45 | 3.5 |
XBD4.2/25-125W | 25 | 0.42 | 1450 | 73 | 22 | 3.5 |
XBD6.3/25-125W | 25 | 0.63 | 1450 | 73 | 30 | 3.5 |
XBD8.4/25-125W | 25 | 0.84 | 1450 | 73 | 45 | 3.5 |
XBD10.5/25-125W | 25 | 1.05 | 1450 | 73 | 55 | 3.5 |
XBD12.6/25-125W | 25 | 1.26 | 1450 | 73 | 75 | 3.5 |
XBD14.7/25-125W | 25 | 1.47 | 1450 | 73 | 75 | 3.5 |
XBD16.8/25-125W | 25 | 1.68 | 1450 | 73 | 90 | 3.5 |
XBD18.9/25-125W | 25 | 1.89 | 1450 | 73 | 90 | 3.5 |
XBD5.8/45-150W | 25 | 0.58 | 1450 | 73 | 45 | 3 |
XBD8.7/45-150W | 25 | 0.87 | 1450 | 73 | 75 | 3 |
XBD11.6/45-150W | 25 | 1.16 | 1450 | 73 | 90 | 3 |
XBD14.5/45-150W | 25 | 1.45 | 1450 | 73 | 110 | 3 |
XBD17.4/45-150W | 25 | 1.74 | 1450 | 73 | 135 | 3 |
XBD20.3/45/150W | 25 | 2.03 | 1450 | 73 | 155 | 3 |
XBD23.2/45-150W | 25 | 2.32 | 1450 | 73 | 180 | 3 |
XBD26.1/45-150W | 25 | 2.61 | 1450 | 73 | 180 | 3 |