Carbon Dioxide Detector/Controller for Fan Switch
Model #: F2000TSM-CO2-8013
CE Approval


F2000TSM-CO2-8013 Carbon Dioxide Detector/Controller Features
• Real-time detecting CO2 level with wall-mounting type
• NDIR infrared CO2 module inside with four CO2 detection range selectable.
• CO2 sensor has Self-Calibration Algorithm and up to 15 years lifetime
• Six indicator lights indicate six CO2 range
• An SPDT relay output with max. 8A to control a 3-wire fan. Two CO2 setpoints selectable for the relay switch by a jumper
• A touch button for operation
• Design for control a ventilator in houses, offices, or other indoor areas
• Wide power range:100~240VAC power supply
• CE-Approval


F2000TSM-CO2-8013 Carbon Dioxide Detector/Controller Specifications

Power supply
100~240VAC
Consumption
1.8 W Max / 230VAC
CO2 sensor
Non-Dispersive Infrared Detector (NDIR)
ABC Logic Self Calibration
CO2 measuring range
0~2,000ppm
Accuracy@25°C(77°F), 2000ppm
±40ppm +3% reading
Stability
<2% of FS over life of sensor
Response time
<2 minutes for 90% step change
Warm up time for turning-on
48 hours (first time), 2 minutes (operation)
6 LED lights
From left to right:
Blue Blue Green Orange Red Red
1st blue light on as CO2 measurement≤600ppm
1st and 2nd blue lights on when 600ppmGreen light on when 800ppmOrange light on when 1,000ppm1st red light on when 1,500ppm1st and 2nd red lights on as CO2 measurement >2,000ppm
Relay control
Max. switch current: 8A (load resistance) SPDT relay
Two CO2 levels selectable to control the relay by jumpers
Two CO2 level selectable
1000ppm/1500ppm
The differential is 300ppm
The shortest protection time for fan turning on/off
10 minutes
Operation conditions
0~50°C(32~122°F); 0~95%RH, non condensing
Storage conditions
0~50°C(32~122°F); 0~80%RH, non condensing
Dimensions/Net weight
100mm x 80mm x 24mm (H x W x D) /180g
Installment standard
65mm x 65mm (2" x 4") wire box
Approval
CE




Contact Supplier

Ms. Ms Rita yu Sales Chat Now
Telephone
86-755-83289036
Mobile
86-15216024218
Fax
86-755-83289052
Skype
Isweek_Rita
Address
16 Floor, Building #3, Zhongke Mansion, Gaoxin South 1st Rd, Hi-Tech Park, Nanshan Shenzhen,Guangdong

You May Like

New Products

Recommended Products

View More View Less

Find Similar Products By Category

Measurement & Analysis Instruments > Analyzers > Gas Analyzers
Categories
Hi~