F2000TSM-CO2-8013 Carbon Dioxide Detector / Controller for Fan Switch
Negotiable /Piece
Min.Order:1 Piece
Carbon Dioxide Detector/Controller for Fan Switch
Model #: F2000TSM-CO2-8013
CE Approval
F2000TSM-CO2-8013 Carbon Dioxide Detector/Controller Features
• Real-time detecting CO2 level with wall-mounting type
• NDIR infrared CO2 module inside with four CO2 detection range selectable.
• CO2 sensor has Self-Calibration Algorithm and up to 15 years lifetime
• Six indicator lights indicate six CO2 range
• An SPDT relay output with max. 8A to control a 3-wire fan. Two CO2 setpoints selectable for the relay switch by a jumper
• A touch button for operation
• Design for control a ventilator in houses, offices, or other indoor areas
• Wide power range:100~240VAC power supply
• CE-Approval
F2000TSM-CO2-8013 Carbon Dioxide Detector/Controller Specifications
Power supply | 100~240VAC |
Consumption | 1.8 W Max / 230VAC |
CO2 sensor | Non-Dispersive Infrared Detector (NDIR) ABC Logic Self Calibration |
CO2 measuring range | 0~2,000ppm |
Accuracy@25°C(77°F), 2000ppm | ±40ppm +3% reading |
Stability | <2% of FS over life of sensor |
Response time | <2 minutes for 90% step change |
Warm up time for turning-on | 48 hours (first time), 2 minutes (operation) |
6 LED lights From left to right: Blue Blue Green Orange Red Red | 1st blue light on as CO2 measurement≤600ppm 1st and 2nd blue lights on when 600ppm |
Relay control | Max. switch current: 8A (load resistance) SPDT relay Two CO2 levels selectable to control the relay by jumpers |
Two CO2 level selectable | 1000ppm/1500ppm The differential is 300ppm |
The shortest protection time for fan turning on/off | 10 minutes |
Operation conditions | 0~50°C(32~122°F); 0~95%RH, non condensing |
Storage conditions | 0~50°C(32~122°F); 0~80%RH, non condensing |
Dimensions/Net weight | 100mm x 80mm x 24mm (H x W x D) /180g |
Installment standard | 65mm x 65mm (2" x 4") wire box |
Approval | CE |