Combined Transformer Substation
Negotiable /Piece
Min.Order:1 Piece
ZHEJIANG SANBIAN GROUP CORPORATION LTD.
1.Summary
ZBW series combined power distribution station is the power distribution equipment combining high voltage transformer.transformer and low voltage equipment that is used for city tall buildings urban&rural buildings,residence communities,medium&small factories,mines,oil fields and temporary electrical power consuming sites. The station function to receive and distribute power energy in power distribution system.
ZBW series combined transformer features compact structure,package unit,safe and reliable operation,convenient maintenance,attractive apperance,bigh mobility and small size.It can be used as loop network power distribution system.It is a new set of equipment for urban&rural transformer substation construction and drenovation.
ZBW series combined substation complies with the standards of GB/T17467-1998 High Voltage/Low Voltage Pre-Installed Transformer substation and IEC1330.
2.Technical Parameters
2.1 High Voltage Switch Panel Parameter Table
Series No |
Name |
Unit |
Parameter |
1 |
Nominal voltage |
kV |
12 |
2 |
Nominal frequency |
Hz |
50 |
3 |
Nominal current |
A |
630 |
4 |
Nominalshort withstanding current |
kA/2S |
20 |
5 |
Nominal short peak current |
kA |
50 |
6 |
Withstanding current when grounding switch is closed for a short time |
kA/2S |
20 |
7 |
Peak current when grounding switch is closed for a short time |
kA |
50 |
8 |
5% nominal on/off current |
A |
31.5 |
9 |
Nominal load on/off current |
A |
630 |
10 |
Drifting current |
A |
1400 |
11 |
Idle transformer on/off current |
A |
16 |
12 |
Fuse combination switch short-circuit on/off current |
kA/2S |
20 |
13 |
On/off current |
kA |
50 |
14 |
1 min power frequency withstand voltage ground,inter-phase/isolation notch |
kV effective value |
42/48 |
15 |
Impulse withstand voltage ground,inter-phase/isolation notch |
kV effective value |
75/85 |
2.2 Transformer Main Technical Parameter Table
Type |
Nominal voltage(Kv) |
Nominal capacitance(kVA) |
S9-M, S11-M |
6,10 |
50-1600 |
SC9 SC10 SG10 |
6,10 |
50-1600 |
2.3 Fuse Parameter Table
Type |
Nominal voltage(kV) |
Nominal on/off current(kA) |
Fuse nominal current(A) |
Fuse specific current(A) |
SFLDJ SFLAJ |
12 |
31.5 |
40 |
6.3 10 16 20 25 31.5 40 |
100 |
50 63 80 100 | |||
125 |
125 | |||
40 |
200 |
160 200 |